Z. BACKFLOW PREVENTERS<br />

1. Reduced Pressure Backflow Preventers (RPBFP):<br />

a. Reduced pressure backflow preventer (2-1/2" thru 8” or 10”): ANSI/ASSE 1013;<br />

complete unit of two independently acting check valves together with an<br />

automatically operating pressure relief valve, two gate valves, <strong>and</strong> four test cocks,<br />

bronze or iron body with bronze internal parts, 150 psi working pressure, <strong>and</strong> shall<br />

comply with AWWA St<strong>and</strong>ard C506.<br />

ACCEPTABLE MANUFACTURERS AND MODELS<br />

Cla-Val Co.<br />

RP-1 (2” & larger)<br />

Watts 909<br />

Hersey<br />

6CM<br />

Febco 825<br />

Wilkins 375<br />

AMES<br />

Silver Bullet – 4000 SS<br />

b. Reduced pressure backflow preventer (2” <strong>and</strong> smaller): ANSI/ASSE 1013; complete<br />

unit of two independently acting check valves together with an automatically<br />

operating pressure relief valve, two ball valves, strainer, <strong>and</strong> four test cocks, bronze<br />

or iron body with bronze internal parts, 150 psi working pressure, <strong>and</strong> shall comply<br />

with AWWA St<strong>and</strong>ard C506.<br />

ACCEPTABLE MANUFACTURERS AND MODELS<br />

Cla-Val Co.<br />

RP-2 (1-1/2” & smaller)<br />

Watts<br />

009QT & 995QT<br />

Hersey<br />

FRP-II<br />

Febco<br />

825Y<br />

Wilkins<br />

975XL<br />

AA. WATER HAMMER ARRESTORS<br />

1. Water Hammer Arrestors (WHA): ANSI A112.26.1, ASSE 1010, <strong>and</strong> PDI WH-201;<br />

permanently sealed bellows or exp<strong>and</strong>ing chamber. Sizing designations indicated on<br />

drawings are st<strong>and</strong>ard classifications established by Plumbing <strong>and</strong> Drainage Institute<br />

"St<strong>and</strong>ard PDI-WH201". Verify that system pressure meets minimum required for water<br />

hammer arrestor provided.<br />

BB. TRAP PRIMERS<br />

ACCEPTABLE MANUFACTURERS AND MODELS<br />

Josam 75000<br />

Jay R. Smith 5000<br />

Wade<br />

"SHOKSTOP" Series<br />

Zurn Z-1700<br />

Sioux Chief<br />

"Hydra-Rester" Series<br />

Watts<br />

No. 15 Series<br />

PPP<br />

SC & SWA Series<br />

Mifab<br />

WHB Series<br />

1. Trap Guard (TG): Smooth, flexible elastomerictrap seal device utilizes a normally closed<br />

seal to prevent evaporation of the liquid trap seal <strong>and</strong> also protects against sewer gases<br />

from backing up into the building or surrounding areas. The device opens when liquid<br />

enters to allow drainage to flow through into the building drainage piping, <strong>and</strong> closes<br />

when there is no drainage flow entering the drain. Provide on all floor, sink, <strong>and</strong> hub<br />

drains connected to the sanitary sewer system or to other systems that may have sewer<br />

gases present in the drainage system. The device must be selected <strong>and</strong> installed in strict<br />

accordance with the manufacturer’s instructions <strong>and</strong> the requirements of the applicable<br />

codes.<br />

Plumbing Systems 22 00 01 - 10<br />

DPR09328