f. Where several pipes can be installed in parallel <strong>and</strong> at same elevation, provide<br />

multiple or trapeze hangers. Consult with project structural engineer for approval.<br />

g. Support riser piping independently of connected horizontal piping.<br />

h. For below floor hanger installations, place one hanger at each pipe penetration thru a<br />

concrete grade beam, at either side, a minimum of 12 inches from the face of the<br />

grade beam.<br />

X. HANGER RODS<br />

1. Steel Hanger Rods: Threaded both ends.<br />

Y. INSERTS<br />

1. Inserts: Malleable iron case of galvanized steel shell <strong>and</strong> exp<strong>and</strong>er plug for threaded<br />

connection with lateral adjustment, top slot for reinforcing rods, lugs for attaching to<br />

forms; size inserts to suit threaded hanger rods.<br />

Z. INSULATION<br />

1. Pipe insulation for domestic hot <strong>and</strong> cold water pipe, roof drains <strong>and</strong> horizontal roof drain<br />

pipe.<br />

a. Heavy duty preformed fiberglass (ASTM C 547, type 1, 2 or 3). Schuller, Knauf or<br />

Certainteed.<br />

b. Preformed flexible elastomeric insulation (ASTM C 534) Armstrong “Armaflex”, or<br />

Schuller “Rubatex”.<br />

c. Preformed unicellular polyolefin foam (ASTM C534) tubular preslit with adhesive.<br />

IMCOA.<br />

INSULATION SCHEDULE<br />

Cold Water<br />

Hot Water<br />

1" thick up to 2" pipe size<br />

1-1/2" thick over 2" pipe size<br />

1" thick up to 2" pipe size<br />

1-1/2" thick over 2" pipe size<br />

d. Provide all purpose jacket, high density white kraft bonded to aluminum foil,<br />

reinforced with fiberglass yarn lap <strong>and</strong> butt, self sealing, pressure sensitive. Schuller<br />

“Micro-Lok”, Certainteed “Snap-On”.<br />

e. PVC fitting covers, one piece pre molded high impact PVC white gloss insulating<br />

fitting covers <strong>and</strong> jackets. Schuller “Zeston 2000PVC”.<br />

2. Fire-Test-Response Characteristics: As determined by testing materials identical to<br />

those specified in this Section according to ASTM E 84, by a testing <strong>and</strong> inspecting<br />

agency acceptable to authorities having jurisdiction. Factory label insulation <strong>and</strong> jacket<br />

materials <strong>and</strong> sealer <strong>and</strong> cement material containers with appropriate markings of<br />

applicable testing <strong>and</strong> inspecting agency.<br />

a. Insulation Installed Indoors: Flame-spread rating of 25 or less, <strong>and</strong> smoke-developed<br />

rating of 50 or less.<br />

b. Insulation Installed Outdoors: Flame-spread rating of 75 or less, <strong>and</strong> smokedeveloped<br />

rating of 150 or less.<br />

AA. PIPING IDENTIFICATION<br />

1. Install manufactured pipe markers indicating service on each piping system. Install with<br />

flow indication arrows showing direction of flow.<br />

a. Pipes with OD, <strong>Inc</strong>luding Insulation, Less Than 6 <strong>Inc</strong>hes: Pre-tensioned pipe<br />

markers. Use size to match pipe <strong>and</strong> ensure a tight fit.<br />

b. Pipes with OD, <strong>Inc</strong>luding Insulation, 6 <strong>Inc</strong>hes <strong>and</strong> Larger: Shaped pipe markers.<br />

Use size to match pipe <strong>and</strong> secure with fasteners.<br />

c. Locate pipe markers <strong>and</strong> color b<strong>and</strong>s on piping as follows: Near each valve <strong>and</strong><br />

control device; Near each branch connection, excluding short takeoffs; Where flow<br />

Plumbing Systems 15400-14<br />

DPR09328