28.04.2015 Views

final bid specs 09328.pdf - Freese and Nichols, Inc.

final bid specs 09328.pdf - Freese and Nichols, Inc.

final bid specs 09328.pdf - Freese and Nichols, Inc.

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

2. Provide batteries with ampere - hour capacity rated at 150% above the minimum required<br />

calculated value (24 hours normal operation plus 5 minutes alarm operation).<br />

F. Voltage Drop Calculations:<br />

1. Provide voltage drop calculations using the lumped load calculation method (all devices<br />

assumed at the end of the circuit). Use the current consumption of the device at its lowest<br />

operating voltage rating.<br />

2. Provide calculations showing that with a supply of 24.0 volts, measured at the point of<br />

connection to the notification circuit, the last device shall have no less than 21.6 volts<br />

measured across its terminals. The last device shall be the device which has the lowest<br />

voltage measured across its terminals as determined by measurements taken from the<br />

FACP to the last device in each leg of a Class A circuit.<br />

3. Size all wiring for a 20% increase in the number of devices <strong>and</strong> conductor length added<br />

to a circuit will not lower the voltage drop at the last device below 21.6 volts as indicated<br />

in paragraph 1.02 (E) (2). <strong>Inc</strong>lude this calculation with the submittal.<br />

4. Calculations shall prove that no individual initiating, signaling or notification appliance circuit<br />

is loaded more than 80% of its capacity. Calculations shall prove that the total connected<br />

load for each remote power supply or FACP power supply is 80% or less of its<br />

capacity.<br />

G. Field quality-control test reports.<br />

H. Operation <strong>and</strong> maintenance data.<br />

I. Submittals to Authorities Having Jurisdiction (AHJ): In addition to distribution requirements<br />

for submittals specified in Division 1 Section "Submittals," make an identical submittal to authorities<br />

having jurisdiction. To facilitate review, include copies of annotated Contract Drawings<br />

as needed to depict component locations. Resubmit if required to make clarifications or<br />

revisions to obtain approval. On receipt of comments from authorities having jurisdiction,<br />

submit them to Architect for review. If special permit fees are required for AHJ review <strong>and</strong><br />

approval, this cost shall be included in the fire alarm contractors <strong>bid</strong>.<br />

J. Documentation:<br />

1. Approval <strong>and</strong> Acceptance: Provide the "Record of Completion" form according to<br />

NFPA 72 to Owner, Architect, <strong>and</strong> authorities having jurisdiction.<br />

2. Record of Completion Documents: Provide the "Permanent Records" according to<br />

NFPA 72 to Owner, Architect, <strong>and</strong> authorities having jurisdiction. Format of the written<br />

sequence of operation shall be the optional input/output matrix.<br />

1.05 QUALITY ASSURANCE<br />

A. The fire alarm installing firm shall be an authorized distributor for the local region in which the<br />

project resides, as defined by the manufacturer of the fire alarm control panel <strong>and</strong> shall have<br />

an office located within 75 miles of the Owner’s facility.<br />

B. The installing firm shall be currently licensed in the State of Texas with an ACR# in good<br />

st<strong>and</strong>ing <strong>and</strong> shall have been in the business of designing, installing <strong>and</strong> servicing commercial<br />

fire alarm/life safety systems for not less than 5 years.<br />

C. The installing firm shall employ a minimum of two (2) persons with training certificates indicating<br />

that same individuals have received factory training to install the manufacturer’s fire alarm<br />

system. Both of these persons must be Texas licensed Fire Alarm Technicians. The certificates<br />

shall indicate that the training has been completed recently, within three (3) years of the<br />

project <strong>bid</strong> date. Only factory-trained individuals will be allowed to install fire alarm devices<br />

<strong>and</strong> wiring.<br />

D. The installing firm shall employ, on a full-time basis, a minimum of one (1) individual who is licensed<br />

by the Texas State Fire Marshal’s Office as a Fire Alarm Planning Superintendent<br />

(APS). Alternatively, this person may be a licensed Fire Protection Engineer.<br />

Fire Alarm <strong>and</strong> Detection System 13 85 10-3<br />

DPR09328

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!