1.05 JOB CONDITIONS<br />
A. The fire protection system piping shall include the piping, all valves, piping, hangers, <strong>and</strong><br />
other necessary appurtenances for a complete <strong>and</strong> operable piping system.<br />
2.00 PRODUCTS<br />
2.01 PIPE AND FITTINGS<br />
A. Pipe Fittings above Grade<br />
1. Ferrous Pipe (welded <strong>and</strong> seamless)<br />
a. Black steel pipe (for fire protection use) (ASTM A795, ANSI/ASTM A53), wrought<br />
steel pipe (ANSI B36.10M), electric resistance welded pipe (ASTM A135); rolled<br />
grooved steel pipe (ASTM A135 or A53).<br />
b. Ferrous fittings, cast-iron threaded, Class 125 (ANSI B16.4) cast-iron flanged<br />
(ANSI B16.1); malleable iron threaded fittings (Class 125) (ANSI B16.3); factory<br />
wrought steel, buttweld (ANSI B16.9), (ANSI B16.25); forged steel, socket<br />
welded or threaded (ANSI B16.11); rigid radius grooved systems (AWWA C606)<br />
250 psig.<br />
2. Copper Pipe <strong>and</strong> Tube (drawn, seamless)<br />
a. Seamless, (ASTM B75/B88); wrought seamless copper <strong>and</strong> copper alloy tube<br />
(ASTM B251) brazed joints (AWS A5.8 Class BCuP-3 or BCuP-4. Solder metal<br />
95-5 tin antimony, grade 95 TA (ASTM B32.<br />
b. Copper fittings; wrought copper <strong>and</strong> bronze solder-joint pressure fittings (ANSI<br />
B16.22); cast bronze solder-joint pressure fittings (ANSI B16.18).<br />
2.02 VALVES, GENERAL PURPOSE<br />
A. Gate Valves<br />
1. Above ground valves; 2-1/2" <strong>and</strong> larger, cast-iron, rising stem, outside screw <strong>and</strong> yoke,<br />
175 psig (ASTM A126, Class B), one piece yoke bonnet, bronze yoke bushings, solid<br />
wedge discs, bronze for 3-1/2" <strong>and</strong> smaller valves, cast-iron with bronze disc ring above<br />
3-1/2" pipe size, flanged 2" <strong>and</strong> smaller, bronze body, rising stem, outside screw <strong>and</strong><br />
yoke, 175 psig, threaded outlet (ANSI/ASME B1.20.1). Acceptable manufacturers:<br />
Stockham, Clow, Central <strong>and</strong> Nibco.<br />
B. Butterfly Valves<br />
1. General: Wafer-type valves with components that extend beyond the valve body shall be<br />
installed in a manner that does not interfere with the operation of any system component.<br />
2. Slow-close, UL listed/FM approved outside indicating style, ductile iron body with EPDM<br />
rubber molded or polymid finish, <strong>and</strong> cast-iron disc, EPDM coated, grooved, or wafer<br />
style ends. Integral supervised open, double pole single throw supervisory tamper<br />
switch. Acceptable manufacturers <strong>and</strong> models: Central, Model A-BFV; Victaulic, Series<br />
708; Grinnell, GRUVLOK.<br />
C. Ball Valves: for Water Shut-off<br />
1. Ball valves 2" <strong>and</strong> less: Rated 175 lb. minimum water, oil, air <strong>and</strong> gas pressure, brass or<br />
bronze construction, seat material as recommended by manufacturer for material<br />
conveying, lever h<strong>and</strong>le, threaded or soldered connections. Throttling valves shall be<br />
provided with memory stops. Acceptable manufacturers <strong>and</strong> models: Crane, 9302,<br />
9322; ITT Grinnell, 3500, 3500SJ; Milwaukee, BA-200, BA-250; Watts, B-6000, B-6001;<br />
Nibco, T-580, S-580.<br />
Facility Fire Suppression Water Service Piping 21 11 00 - 3<br />
DPR09328