26 28 16 ENCLOSED SWITCHES AND CIRCUIT BREAKERS<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install disconnects. Electrical<br />

work shall be in accordance with Section 26 05 00, COMMON WORK RESULTS FOR<br />

ELECTRICAL.<br />

1.02 QUALITY ASSURANCE - ACCEPTABLE MANUFACTURERS<br />

Disconnects shall comply with the specifications <strong>and</strong> shall be by the following Manufacturers:<br />

A. Eaton Cutler-Hammer<br />

B. General Electric<br />

C. Square D<br />

1.03 SUBMITTALS<br />

Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include:<br />

A. Disconnects<br />

1.04 STANDARDS<br />

The applicable provisions shall apply as if written here in their entirety:<br />

ANSI/UL - 198E<br />

NEMA RS1<br />

Fed. Spec. FS-WS-865<br />

2.00 PRODUCTS<br />

2.01 MANUFACTURED PRODUCTS<br />

A. DISCONNECT SWITCHES: Class "R" or non-fusible; of the required ampere rating, or as<br />

indicated on the plans; heavy duty, quick-make, quick-break, 3-phase, 3-pole switches, unless<br />

otherwise indicated.<br />

B. ENCLOSURES: NEMA 1 for air conditioned spaces, NEMA 12 for ventilated areas, NEMA<br />

3R for exterior locations <strong>and</strong> NEMA 4X, 304 stainless steel for corrosive areas. Furnish<br />

enclosures with interlocking covers with maintenance defeat feature <strong>and</strong> external frontoperated<br />

flange-mounted switch levers. Disconnects shall have provisions for the use of<br />

three (3) safety padlocks in the "Off" position. Furnish horsepower rated switches for motor<br />

circuits. The fuse interrupting rating shall be 65,000 rms amperes.<br />

Enclosed Switches <strong>and</strong> Circuit Breakers 26 28 16-1<br />