B. Combination starter doors shall be interlocked mechanically with the circuit breaker operator<br />

mechanism to prevent unintentional opening of the door while the circuit breaker is in the<br />

closed position. The circuit breaker operator mechanism shall be mounted on the stationary<br />

part of the enclosure <strong>and</strong> not on the door of the enclosure. The circuit breaker operator mechanism<br />

shall indicate "ON" <strong>and</strong> "OFF" with the door open or closed. The circuit breaker<br />

shall be manually operated, resettable after trip from the operator mechanism h<strong>and</strong>le. The<br />

operating h<strong>and</strong>le shall clearly indicate whether the circuit breaker is "ON" or "OFF", or<br />

"TRIPPED". Means shall be provided to lock each operator mechanism h<strong>and</strong>le in the "OFF"<br />

position <strong>and</strong> to close the door. Means shall be provided for releasing the interlock for intentional<br />

access to the interior at any time <strong>and</strong> intentional application of power, if desired, while<br />

door is open. Padlocking arrangements shall permit locking the disconnect device "OFF" with<br />

at least three padlocks with door closed or open.<br />

C. The combination starter shall have a magnetic starter contactor. The magnetic starter contactor<br />

shall be NEMA rated <strong>and</strong> NEMA 1 magnetic starter contactors shall be the minimum<br />

size allowed. Magnetic starter contactors shall have renewable contacts <strong>and</strong> a renewable<br />

coil which shall allow each to be replaced without replacing other parts of the magnetic starter<br />

contactor. Magnetic starter contactors shall have a maximum pick up voltage of 71% of nominal<br />

coil voltage <strong>and</strong> a maximum drop out voltage of 59% of nominal coil voltage.<br />

D. Each magnetic starter shall have three (3) external manual reset thermal overload relays of<br />

either the bimetallic type or the melting alloy type. Overload relays shall be either ambient<br />

compensated or ambient insensitive. Overload relay heaters shall be Class 10 for submersible<br />

pump motors <strong>and</strong> hermetically sealed motors <strong>and</strong> shall be Class 20 for all other motors.<br />

Overload relay heaters shall be selected to produce an overload trip at no more than the following<br />

percent of the motor nameplate full load current rating:<br />

Motors with a marked service factor not<br />

less than 1.15 125%<br />

Motors with a marked temperature rise of<br />

not over 40°C 125%<br />

All other motors 115%<br />

E. Overload relays shall be reset from outside the enclosure with an insulated bar or button.<br />

Auxiliary contacts shall be furnished on the circuit breaker operating mechanism, the starter<br />

contactor <strong>and</strong> on the overload sensing unit as shown on the plans.<br />

F. Controls <strong>and</strong> lights shall be heavy duty oiltight construction. Devices installed in the combination<br />

starter or on the door of the combination starter shall be completely factory wired with<br />

connections to external devices brought to a terminal strip installed in the starter. No field<br />

wiring shall be permitted except for connections to remote devices from the terminal strip. A<br />

physical wiring diagram shall be provided on each enclosure door <strong>and</strong> shall be protected to<br />

remain intact <strong>and</strong> legible for the service life of the equipment. Control devices shall be identified<br />

as to type <strong>and</strong> manufacturer.<br />

G. Control relays, timing relays, control transformers, control circuit fuse blocks, etc., shall be<br />

grouped in the corresponding combination starter with control wiring kept as short as possible.<br />

Ample space shall be allowed between devices so that each component is completely<br />

accessible without removing any other device.<br />

Enclosed Controllers 26 29 13 - 4<br />

DRP09328