26 05 33.03 OUTLET BOXES<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install outlet boxes. Electrical<br />

work shall be in accordance with Section 26 05 00, COMMON WORK RESULTS FOR<br />

ELECTRICAL.<br />

1.02 QUALITY ASSURANCE - ACCEPTABLE MANUFACTURERS<br />

Steel City Series 600<br />

1.03 SUBMITTALS<br />

No submittals required for Section 26 05 33.03, OUTLET BOXES.<br />

1.04 STANDARDS<br />

The applicable provisions of the following st<strong>and</strong>ards shall apply as if written here in their entirety:<br />

ANSI/NEMA OS 1<br />

ANSI/NEMA OS 2<br />

Sheet steel outlet boxes, device boxes, covers <strong>and</strong> box supports.<br />

Non-metallic outlet boxes, device boxes, covers <strong>and</strong> box supports.<br />

2.00 PRODUCTS<br />

2.01 MATERIALS<br />

A. GENERAL: Furnish boxes with proper covers <strong>and</strong> device plates<br />

B. CAST BOXES: Cast feralloy metal, deep type, gasketed cover, threaded hubs <strong>and</strong> integral<br />

mounting lugs. Use cast boxes for damp <strong>and</strong> outdoor installation. Boxes shall be<br />

manufactured by Crouse-Hinds, Appleton or approved equal.<br />

3.00 EXECUTION<br />

3.01 PREPARATION; COORDINATION OF BOX LOCATIONS<br />

A. Provide electrical boxes in the locations shown on the Plans, <strong>and</strong> as required for splices, taps,<br />

wire pulling, equipment connections, <strong>and</strong> code compliance.<br />

B. Electrical box locations shown on Contract Drawings are approximate unless dimensioned.<br />

Verify locations of boxes <strong>and</strong> outlets prior to rough-in. Outlet locations may be modified to<br />

accommodate changes in door swings, space changes or to clear other interferences that<br />

arise or from job modifications. Make such modifications at no cost to the OWNER as a<br />

matter of job coordination. Coordinate job conditions <strong>and</strong> notify the ENGINEER of<br />

discrepancies before proceeding with the installation of the work. Set wall boxes in advance<br />

of wall construction blocked in place, <strong>and</strong> secured. Set wall boxes flush with the finish. Install<br />

extension sleeves as required to extend boxes to finished surfaces.<br />

Outlet Boxes 26 05 33.03-1<br />