C. Unless otherwise noted, location of outlet boxes shall be as follows:<br />

Equipment or Outlets<br />

Toggle switches<br />

Receptacles<br />

Elevation *(A.F.F.)<br />

4'0"<br />

1'6"<br />

Equipment or Outlets Elevation *(A.F.F.)<br />

Flow/Level Transmitters<br />

5'5"<br />

Circular Chart Recorder<br />

5'5"<br />

Motor starters<br />

5'0"<br />

Control stations<br />

4'0"<br />

Manual starters<br />

5'0"<br />

Thermostats in office areas<br />

4'0"<br />

Telephone outlets<br />

1'6"<br />

Circuit protective devices<br />

6'6" to top of<br />

enclosure<br />

* Above Finished Floor.<br />

D. Locate <strong>and</strong> install boxes to allow access. Where installation is inaccessible, coordinate<br />

locations <strong>and</strong> sizes of required access doors in accordance with other sections of the<br />

specifications.<br />

3.02 INSTALLATION<br />

A. Do not install boxes back-to-back in walls. Provide minimum 6" separation, except provide<br />

minimum 24" separation in acoustic-rated walls.<br />

B. Locate boxes in masonry walls to require cutting of masonry unit corner only. Coordinate<br />

masonry cutting to achieve neat openings for boxes.<br />

C. Provide knockout closures for unused openings.<br />

D. Use multiple-gang boxes where more than one (1) device is installed together; do not use<br />

sectional boxes. Provide barriers to separate wiring of different voltage systems.<br />

E. Install boxes in walls without damaging wall insulation.<br />

F. Provide recessed outlet boxes in finished areas; secure boxes to interior wall <strong>and</strong> partition<br />

studs, position to allow for surface finish thickness. Use stamped steel stud bridges for flush<br />

outlets in hollow stud wall, <strong>and</strong> adjustable steel channel fasteners for flush ceiling outlet<br />

boxes.<br />

G. Align wall-mounted outlet boxes for switches, thermostats <strong>and</strong> similar devices.<br />

END OF SECTION<br />

Outlet Boxes 26 05 33.03-2<br />

DRP09328