B. Hydrostatically test fire systems at not less than 200 psig for two (2) hours, or at 50 psig in<br />

excess of the maximum static pressure when the static pressure exceeds 215 psig. Measure<br />

hydrostatic pressure at the low point of the system being tested.<br />

C. Prepare a Material <strong>and</strong> Test Certificate, in accordance with NFPA 13. Obtain certificates of<br />

approval from regulatory authorities. Submit certificates in the <strong>final</strong> submittal data to the<br />

Engineer.<br />

END OF SECTION<br />

Facility Fire Suppression Water Service Piping 21 11 00 - 6<br />

DPR09328