P. At each convenience outlet, install a grounding clip attached to the outlet box <strong>and</strong> leave a<br />

sufficient length of #12 wire with green-colored insulation to connect to the grounding terminal<br />

at the receptacle.<br />

Q. Grounding Manholes <strong>and</strong> H<strong>and</strong>holes: Install a driven ground rod through manhole or<br />

h<strong>and</strong>hole floor, close to wall, <strong>and</strong> set rod depth so 4 inches will extend above finished floor. If<br />

necessary, install ground rod before manhole is placed <strong>and</strong> provide No. 1/0 AWG bare,<br />

tinned-copper conductor from ground rod into manhole through a waterproof sleeve in<br />

manhole wall. Protect ground rods passing through concrete floor with a double wrapping of<br />

pressure-sensitive insulating tape or heat-shrunk insulating sleeve from 2 inches above to 6<br />

inches below concrete. Seal floor opening with waterproof, nonshrink grout.<br />

R. Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts,<br />

cable racks, pulling irons, ladders, <strong>and</strong> cable shields within each manhole or h<strong>and</strong>hole, to<br />

ground rod or grounding conductor. Make connections with No. 4 AWG minimum, str<strong>and</strong>ed,<br />

hard-drawn copper bonding conductor. Train conductors level or plumb around corners <strong>and</strong><br />

fasten to manhole walls.<br />

3.02 INSPECTION<br />

A. Inspect the grounding <strong>and</strong> bonding system conductors <strong>and</strong> connections for tightness <strong>and</strong><br />

proper installation.<br />

B. Use Biddle Direct Reading Earth Resistance Tester or equivalent to measure resistance to<br />

ground of the system. Perform testing in accordance with the test instrument manufacturer’s<br />

recommendation using the fall of potential method.<br />

C. All test equipment provided under this section shall be approved by the ENGINEER.<br />

D. Resistance to ground testing shall be performed during dry season. Submit test results in the<br />

form of a graph showing the number of points measured (12 minimum) <strong>and</strong> the numerical<br />

resistance to ground.<br />

E. Testing shall be performed before energizing the distribution system.<br />

F. A separate test shall be conducted for each building or system.<br />

G. Notify the ENGINEER immediately if the resistance to ground for any building or system is<br />

greater than five ohms. Provide additional ground rods <strong>and</strong> conductors as required to bring<br />

the resistance to five ohms.<br />

END OF SECTION<br />

Grounding & Bonding for Electrical Systems 26 05 26-4<br />