26 28 00 LOW VOLTAGE PROTECTIVE DEVICES<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidents to install overcurrent protective devices.<br />

Electrical work shall be in accordance with Section 26 05 00, COMMON WORK RESULTS FOR<br />

ELECTRICAL.<br />

1.02 SUBMITTALS<br />

Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include Record<br />

Data for:<br />

A. Fuses<br />

B. Circuit Breakers<br />

2.00 PRODUCTS<br />

2.01 MATERIALS<br />

A. FUSES: Current-limiting with 200,000 rms symmetrical amperes interrupting rating <strong>and</strong> U.L.<br />

listed, manufactured by Bussmann, Ferraz Shawmut or Littlefuse. All fuses shall be by the<br />

same Manufacturer. Fuses which are 600 amperes <strong>and</strong> smaller shall be Class RK1, dual<br />

element, <strong>and</strong> have separated overload <strong>and</strong> short-circuit elements. The overload, time delay<br />

element shall be spring-activated <strong>and</strong> utilize a eutectic alloy with a 284 degrees F. melting<br />

point. The fuse shall hold 500% of its rated fuse current for a minimum of 10 seconds.<br />

B. CIRCUIT BREAKERS: Bolt-on, thermal magnetic circuit breakers with the number of poles<br />

<strong>and</strong> the ampere rating as indicated on the plans; capable of interrupting the symmetrical fault<br />

current available to them; manufactured by Cutler-Hammer, General Electric or Square D.<br />

Series rating of breakers shall not be permitted. Circuit breakers installed in existing<br />

equipment shall match make, manufacturer <strong>and</strong> AIC rating of existing equipment where being<br />

installed.<br />

3.00 EXECUTION<br />

3.01 INSTALLATION<br />

A. Install fuses in switches as scheduled. Install fuses on the line side of ballast-controlled light<br />

fixtures when indicated. The fuses shall be sized by the fixture Manufacturer.<br />

B. Unless otherwise indicated, mount the protective devices with the top of the cabinet or<br />

enclosure at a maximum of 6'-6" above the finished floor. Properly align the protective<br />

devices <strong>and</strong> adequately support them independently of the connecting raceways. Furnish <strong>and</strong><br />

install all components necessary for the support of the equipment when the building is not<br />

suitable for direct mounting upon it.<br />

C. Install overcurrent devices in accordance with the National Electrical Code.<br />

END OF SECTION<br />

Low Voltage Protective Devices 26 28 00-1<br />