26 29 13 ENCLOSED CONTROLLERS<br />

1.00 GENERAL<br />

1.01 WORK INCLLUDED<br />

A. Furnish labor, materials, equipment <strong>and</strong> incidentals to install combination motor starters.<br />

Electrical work shall be in accordance with Section 26 05 00, COMMON WORK RESULTS<br />

FOR ELECTRICAL. Section includes the following enclosed controllers rated 600 V <strong>and</strong> less:<br />

1.02 QUALITY ASSURANCE - ACCEPTABLE MANUFACTURERS<br />

A. Enclosed Controllers shall comply with the specifications <strong>and</strong> shall be by the following Manufacturers:<br />

1. Allen Bradley<br />

2. Eaton Cutler-Hammer<br />

3. General Electric<br />

4. Square D<br />

1.03 QUALITY ASSURANCE<br />

A. Electrical Components, Devices, <strong>and</strong> Accessories: Listed <strong>and</strong> labeled as defined in <strong>and</strong><br />

marked for intended location <strong>and</strong> application.<br />

B. Comply with NFPA 70.<br />

C. Coordinate with equipment suppliers for actual motor data – HP, voltage, amps, etc, to properly<br />

size controller (starter) <strong>and</strong> overloads.<br />

1.04 SUBMITTALS<br />

Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include:<br />

A. Shop Drawings: For each enclosed controller.<br />

1. <strong>Inc</strong>lude dimensioned plans, elevations, sections, details, <strong>and</strong> required clearances <strong>and</strong><br />

service spaces around controller enclosures.<br />

2. <strong>Inc</strong>lude manufacturer's technical data on features, performance, electrical characteristics,<br />

ratings, <strong>and</strong> enclosure types <strong>and</strong> finishes. Data sheets shall clearly identify the make <strong>and</strong><br />

model number of the equipment being provided.<br />

3. Show tabulations of the following:<br />

a. Each installed unit's type <strong>and</strong> details.<br />

b. Factory-installed devices.<br />

c. Nameplate legends.<br />

d. Short-circuit current rating of integrated unit.<br />

e. Features, characteristics, ratings, <strong>and</strong> factory settings of individual overcurrent<br />

protective devices in combination controllers.<br />

f. Project specific wiring diagrams/control schematics: For power, signal, <strong>and</strong> control<br />

wiring.<br />

Enclosed Controllers 26 29 13 - 1<br />

DRP09328