E. Electrical Components, Devices, <strong>and</strong> Accessories: Listed <strong>and</strong> labeled as defined in<br />

NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, <strong>and</strong><br />

marked for intended use.<br />

2.00 PRODUCTS<br />

2.01 MANUFACTURERS<br />

A. Subject to compliance with requirements, provide all new products by one of the following:<br />

1. FACP <strong>and</strong> Equipment:<br />

a. Edwards Systems Technology <strong>Inc</strong>.<br />

b. Honeywell International <strong>Inc</strong>.<br />

c. NOTIFIER.<br />

d. Silent Knight.<br />

e. Gamewell-FCI.<br />

f. Approved equal.<br />

2. Wire <strong>and</strong> Cable shall be as recommended by the system manufacturer or one of the following:<br />

a. Comtran Corporation.<br />

b. Helix/HiTemp Cables, <strong>Inc</strong>.<br />

c. Rockbestos-Suprenant Cable Corporation.<br />

a. DRAKA USA.<br />

b. West Penn Wire/CDT.<br />

3. Audible <strong>and</strong> Visual Devices:<br />

a. As manufactured by the FACP manufacturer.<br />

b. System Sensor.<br />

c. Wheelock.<br />

d. Approved equal.<br />

2.02 FACP<br />

A. General Description:<br />

1. Modular, power-limited design with electronic modules, UL 864 listed.<br />

2. Addressable control circuits for operation of mechanical equipment.<br />

B. Alphanumeric Display <strong>and</strong> System Controls: Arranged for interface between human operator<br />

at the FACP <strong>and</strong> addressable system components including annunciation <strong>and</strong> supervision.<br />

Display time <strong>and</strong> date, alarm, supervisory, <strong>and</strong> component status messages <strong>and</strong> the programming<br />

<strong>and</strong> control menu.<br />

1. Annunciator <strong>and</strong> Display: Liquid-crystal type, two line(s) of 20 characters, minimum.<br />

2. Keypad: Arranged to permit entry <strong>and</strong> execution of programming, display, <strong>and</strong> control<br />

comm<strong>and</strong>s.<br />

3. Alarm History: Capability to display/call-up alarm history report for a minimum of 500<br />

events at this display shall be provided.<br />

4. It shall be possible to view a sensitivity test report from this display for all smoke detectors<br />

connected to the system.<br />

C. Circuits:<br />

1. Signaling Line Circuits: NFPA 72, Class A, Style 6.<br />

Fire Alarm <strong>and</strong> Detection System 13 85 10-4<br />