B. SINGLE CONDUCTORS: Conductor with thermoplastic insulation rated at 600 volts <strong>and</strong><br />

insulated with XHHW-2 insulation. Wire shall be water tank tested <strong>and</strong> approved as machine<br />

tool wire, in accordance with National Machine Tool Builders Association. Wire in light fixture<br />

channels <strong>and</strong> other special locations shall be as specifically noted for temperature in NEC<br />

Article 300. Wire shall be manufactured by Southwire, Okonite, General Cable, <strong>and</strong> Houston<br />

Wire & Cable<br />

C. GROUND WIRE: Class B str<strong>and</strong>ed tin-plated conductor without insulation shall be used for<br />

outdoor buried applications, green insulation for ground wires in raceways.<br />

2.02 CONNECTORS AND SPLICES<br />

A. Manufacturers: Subject to compliance with requirements, provide products by one of the<br />

following:<br />

1. AFC Cable Systems, <strong>Inc</strong>.<br />

2. Hubbell Power Systems, <strong>Inc</strong>.<br />

3. O-Z/Gedney; EGS Electrical Group LLC.<br />

4. 3M; Electrical Products Division.<br />

5. Tyco Electronics Corp.<br />

B. Description: Factory-fabricated connectors <strong>and</strong> splices of size, ampacity rating, material,<br />

type, <strong>and</strong> class for application <strong>and</strong> service indicated.<br />

3.00 EXECUTION<br />

3.01 PREPARATION<br />

Completely swab raceway system before installing conductors. Do not use cleaning agents <strong>and</strong><br />

lubricants which have a deleterious effect on the conductors or their insulation.<br />

3.02 INSTALLATION<br />

A. GENERAL<br />

1. Conductors shall be continuous from terminal block to terminal block without splice.<br />

Condulet type fittings shall not contain splices. No splicing of conductors shall be<br />

performed in any below ground structure.<br />

2. Splice only in junction or outlet boxes for branch circuits. Splices for all other circuits shall<br />

be disallowed. Neatly train wiring inside boxes, equipment <strong>and</strong> panelboards. Pull<br />

conductors into a raceway at the same time <strong>and</strong> use U.L. listed, water based, wire pulling<br />

lubricant for pulling No. 4AWG <strong>and</strong> larger wire. Install raceway first as a complete system<br />

without conductors. Do not install pull wires <strong>and</strong> conductors until the raceway system is in<br />

place.<br />

3. Grouping conductors together into one conduit shall not be allowed where the plans<br />

indicate the conductors to be placed in separate conduits. Each home run shown on the<br />

plans shall be in its own conduit.<br />

4. Properly support cables in accordance with the NEC <strong>and</strong> manufacturer’s<br />

recommendations in all raceways. Provide strain relief as required.<br />

5. The cable shall not be bent to a radius no smaller than the manufacturer cable’s minimum<br />

bending radius.<br />

6. Sharing of neutrals in not allowed.<br />

7. Verify all cables <strong>and</strong> conductors by field telephone communications. Any conductor not<br />

tested as specified will be de-terminated, tested <strong>and</strong> re-terminated at the Contractor’s<br />

expense. Payment will not be made for the work until the test has been done.<br />

Low Voltage Electrical Power Conductors & Cables 26 05 19-2<br />

DRP09328