23 81 26 SPLIT-SYSTEM AIR-CONDITIONING UNITS<br />

1.00 GENERAL<br />

1.01 RELATED DOCUMENTS<br />

A. Drawings <strong>and</strong> general provisions of the Contract, including General <strong>and</strong> Supplementary Conditions<br />

<strong>and</strong> Division 1 Specification Sections, apply to this Section.<br />

1.02 SUMMARY<br />

A. This Section includes split-system air-conditioning <strong>and</strong> heat pump units consisting of separate<br />

evaporator-fan <strong>and</strong> compressor-condenser components. Units are designed for exposed<br />

or concealed mounting, <strong>and</strong> may be connected to ducts.<br />

1.03 DEFINITIONS<br />

A. Evaporator-Fan Unit: The part of the split-system air-conditioning unit that contains a coil for<br />

cooling (heat rejection for heating operation in heat pump units) <strong>and</strong> a fan to circulate air to<br />

conditioned space.<br />

B. Compressor-Condenser Unit: The part of the split-system air-conditioning unit that contains a<br />

refrigerant compressor <strong>and</strong> a coil for condensing refrigerant (evaporator for heating operation<br />

in heat pump units).<br />

1.04 SUBMITTALS<br />

A. Product Data: <strong>Inc</strong>lude rated capacities; shipping, installed, <strong>and</strong> operating weights; furnished<br />

specialties; <strong>and</strong> accessories for each type of product indicated. <strong>Inc</strong>lude performance data in<br />

terms of capacities, outlet velocities, static pressures, sound power characteristics, motor requirements,<br />

<strong>and</strong> electrical characteristics.<br />

B. Warranties: Special warranties specified in this Section.<br />

1.05 QUALITY ASSURANCE<br />

A. Electrical Components, Devices, <strong>and</strong> Accessories: Listed <strong>and</strong> labeled as defined in<br />

NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, <strong>and</strong><br />

marked for intended use.<br />

1.06 COORDINATION<br />

A. Coordinate size <strong>and</strong> location of concrete bases for units. Cast anchor-bolt inserts into bases.<br />

Concrete, reinforcement, <strong>and</strong> formwork are specified in Division 3.<br />

B. Coordinate size, location, <strong>and</strong> connection details with equipment supports.<br />

1.07 WARRANTY<br />

A. General Warranty: Special warranty specified in this Article shall not deprive Owner of other<br />

rights Owner may have under other provisions of the Contract Documents <strong>and</strong> shall be in ad-<br />

Split System Air Conditioning Units 23 81 26 - 1<br />