D. LAMPS<br />

1. FLUORESCENT: Cool white; rapid start, unless otherwise specified or indicated.<br />

2. METAL HALIDE: Phosphor-coated, unless otherwise specified or indicated; selfextinguishing<br />

type when the outer lamp envelope is broken.<br />

E. EXIT LIGHTS: Single or double face unit as required for each location, with arrows to clearly<br />

define the path of egress <strong>and</strong> which flash at a rate not exceeding five (5) hertz. Provide<br />

battery-powered exit lights if the exits lights are not served with an emergency power source.<br />

3.00 EXECUTION<br />

3.01 INSTALLATION<br />

A. Provide the lighting fixtures, as specified <strong>and</strong> scheduled on the plans. If a type designation is<br />

omitted, verify the fixture selection with the ENGINEER before installation.<br />

B. Check the architectural finishes <strong>and</strong> provide fixtures with proper trim, frames, support hangers<br />

<strong>and</strong> other hardware required to coordinate with the proper finishes, regardless of the specified<br />

or scheduled catalog number, prefixes <strong>and</strong> suffixes.<br />

C. Fixtures which are t<strong>and</strong>em-mounted <strong>and</strong> recessed in gypboard or plaster ceilings shall be<br />

yoke-mounted.<br />

D. Test <strong>and</strong> aim flood lights, when dark outside to provide a uniform <strong>and</strong> widespread, illuminated<br />

area. Direct units as indicated or instructed by the ENGINEER to prevent objectionable glare.<br />

E. Furnish <strong>and</strong> install photocells where indicated on the plans. Cells shall face a northerly<br />

direction.<br />

F. Furnish <strong>and</strong> install exit lights where scheduled <strong>and</strong> indicated on the plans. Locate fixtures on<br />

the ceiling or wall, as required by the ENGINEER. Provide relays <strong>and</strong> the necessary wiring to<br />

provide a flashing exit light system upon the activation of a fire alarm. Install exit lights in<br />

accordance with Paragraph (Q)(2) of the H<strong>and</strong>icapped Accessibility Act of Texas.<br />

G. Furnish <strong>and</strong> install a complete exterior lighting control system, as indicated on the plans.<br />

Provide materials <strong>and</strong> equipment to properly interface timing devices <strong>and</strong> photocells with<br />

relays <strong>and</strong> contactors so that a complete <strong>and</strong> satisfactory operating system is rendered.<br />

3.02 CLEAN AND ADJUST<br />

Immediately before <strong>final</strong> inspection, clean all fixtures, inside <strong>and</strong> out, including plastics <strong>and</strong><br />

glassware. Adjust all trim to properly fit adjacent surfaces. Replace broken or damaged parts.<br />

Lamp <strong>and</strong> test all fixtures for electrical, as well as, mechanical operation.<br />

END OF SECTION<br />

Lighting 26 50 00-2<br />