28.04.2015 Views

final bid specs 09328.pdf - Freese and Nichols, Inc.

final bid specs 09328.pdf - Freese and Nichols, Inc.

final bid specs 09328.pdf - Freese and Nichols, Inc.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2. Grade underground <strong>and</strong> outdoor conduits to drain free of condensation <strong>and</strong> moisture.<br />

Provide for automatic draining at lowpoints. Install horizontal runs of conduit to provide a<br />

natural drain for condensation without pockets or traps where moisture may collect.<br />

3. Underground conduits shall drain to an underground structure with a floor drain, such as a<br />

manhole or a building basement.<br />

4. Install conduit drain assemblies in outside or underground conduits to provide for draining.<br />

5. Underground conduit bends shall have a minimum 2' bend radius. Underground conduit<br />

bends which are 45 degrees or more <strong>and</strong> which are on conduits of 2" or greater shall<br />

utilize factory pvc coated rigid steel bends.<br />

6. Minimum size for underground conduits is 1”.<br />

7. Contractor shall install duct bank spacers every 8 feet.<br />

8. Conduit shall slope uniformly at not less than 4” per 100’, or more than 60” per 100’<br />

unless indicated otherwise on the plans or approved by the Engineer. Arrange duct banks<br />

to drain into manholes with no low pockets in the duct runs.<br />

C. ROUTING AND SUPPORT<br />

1. Use the conduit route where shown on the plans. Route conduits that do not have a<br />

specified route in the most direct path between the two points, i.e. home runs shown with<br />

an arrow symbol. Route conduits parallel to building lines. Concealed conduits on the<br />

plans shall be below grade, within walls, or above ceilings.<br />

2. Route conduit through roof openings for piping <strong>and</strong> ductwork where possible. Otherwise,<br />

route conduit through the roof with pitch pocket. Conduit shall not penetrate ductwork.<br />

Exposed conduit shall not be installed on the roof without the ENGINEER's prior approval.<br />

3. Install conduit at elevations which maintain headroom, <strong>and</strong> at locations which avoid<br />

interference with other work requiring grading of pipe, the structure, finished walls, etc.<br />

Avoid crossing other work. Conduits shall not be placed in close proximity to equipment,<br />

systems, <strong>and</strong> service lines. Maintain a minimum of 3" separation, except in crossing<br />

which shall be a minimum of 1". Conduits shall not be installed/concealed in water<br />

bearing walls.<br />

4. Conduits in buildings shall be exposed on unfinished ceilings <strong>and</strong> basements, as shown<br />

on the plans. Rigidly support conduits to the building structures using hardware bolted or<br />

screwed to the structure. The mounting hardware shall not mount the conduit directly on<br />

concrete walls <strong>and</strong> ceilings, but shall space the conduit away from the surfaces using<br />

mineralac-type hardware, strut channel clamps, or one hole straps with clamp backs.<br />

5. Provide expansion fittings at expansion, construction <strong>and</strong> seismic joints. Provide<br />

combination expansion/deflection fittings where conduits are concealed at these joints.<br />

6. Group conduit in parallel runs where practical. Use a conduit rack constructed of<br />

channels with conduit straps or clamps. Provide space for an additional 25% conduit.<br />

7. Parallel runs of conduit shall have bends <strong>and</strong> offsets made a the same point such that the<br />

angle of bend is the same in each conduit <strong>and</strong> the conduits remain parallel throughout the<br />

run. Conduits not installed in this manner shall be removed <strong>and</strong> reinstalled at the<br />

Contractor’s expense. Conductors that are installed shall be removed <strong>and</strong> replaced at the<br />

Contractor’s expense.<br />

8. Conduits installed in parallel shall be arranged such that crossings are eliminated.<br />

9. Rigid aluminum conduit systems shall utilize aluminum straps, clamps <strong>and</strong> strut channel.<br />

Coated rigid steel or aluminum conduit shall utilize PVC factory coated or fiberglass<br />

straps, clamps <strong>and</strong> thread rods, etc. as manufactured by Robroy.<br />

10. Nuts, bolts, concrete anchor bolts <strong>and</strong> other metallic fasteners shall be 316 stainless<br />

steel.<br />

Conduits 26 05 33.01-5<br />

DRP09328

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!