D. Bituminous Paint: Cold-applied asphalt emulsion complying with ASTM D 1187.<br />

2.03 FABRICATION, GENERAL<br />

A. Fabricate frames to fit in openings of sizes indicated, with allowances made for fabrication<br />

<strong>and</strong> installation tolerances, adjoining material tolerances, <strong>and</strong> perimeter sealant joints.<br />

B. Join frame members to each other <strong>and</strong> to louver blades with fillet welds, threaded fasteners,<br />

or both, as st<strong>and</strong>ard with louver manufacturer, concealed from view.<br />

2.04 FIXED, EXTRUDED-ALUMINUM LOUVERS<br />

A. Drainable-Blade Louver:<br />

1. Basis-of-Design Product: Ruskin; extruded aluminum stationary louver; ESD-403 or a<br />

comparable product.<br />

2. Frame <strong>and</strong> Blade Nominal Thickness: Not less than 0.080 inch (1.5 mm) for blades <strong>and</strong><br />

0.080 inch (2.0 mm) for frames.<br />

3. Performance Requirements:<br />

a. Free Area: Not less than 8.0 sq. ft. (0.74 sq. m) for 48-inch- (1.2-m-) wide by 48-<br />

inch- (1.2-m-) high louver.<br />

b. Point of Beginning Water Penetration: Not less than 1000 fpm (5.1 m/s).<br />

c. Air Performance: Not more than 0.15-inch wg (37-Pa) static pressure drop at 950-<br />

fpm (4.8-m/s) free-area velocity.<br />

4. AMCA Seal: Mark units with AMCA Certified Ratings Seal.<br />

2.05 COMBINATION, EXTRUDED-ALUMINUM LOUVERS<br />

A. Dual-Blade, Drainable-Blade, Combination Louver: Fixed drainable blades <strong>and</strong> adjustable<br />

plain blades combined in single frame.<br />

1. Basis-of-Design Product: Ruskin; extruded aluminum combination louver; ELC6375D or<br />

a comparable product.<br />

2. Louver Depth: 6 inches (150 mm)<br />

3. Performance Requirements:<br />

a. Free Area: Not less than 7.0 sq. ft. (0.65 sq. m) for 48-inch- (1.2-m-) wide by 48-<br />

inch- (1.2-m-) high louver.<br />

b. Point of Beginning Water Penetration: Not less than 1000 fpm (5.1 m/s).<br />

c. Air Performance: Not more than 0.10-inch wg (25-Pa) static pressure drop at 900-<br />

fpm (4.6-m/s) free-area velocity.<br />

d. Air Leakage: Not more than 0.45 cfm per sq. ft. of louver gross area at a differential<br />

static pressure of 0.15-inch wg (37 Pa) with adjustable louver blades closed.<br />

4. AMCA Seal: Mark units with AMCA Certified Ratings Seal.<br />

B. Electrical Operators:<br />

1. Electrical operators shall have two (2) positions: power open, spring close, operating on a<br />

120 volt control circuit.<br />

2. Electrical operators shall be surface mounted near the louver with connecting rods <strong>and</strong><br />

linkage exposed to the inside space.<br />

2.06 LOUVER SCREENS<br />

A. General: Provide screen at interior face of each exterior louver.<br />

Louvers <strong>and</strong> Vents 08 90 00 - 2<br />

DPR09328