26 05 33.02 WIREWAYS<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install a complete wireway<br />

system. Electrical work shall be in accordance with Section 26 05 00, COMMON WORK<br />

RESULTS FOR ELECTRICAL. Contractor shall size wireways in accordance with the National<br />

Electrical Code.<br />

1.02 SUBMITTALS<br />

Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include Record<br />

Data for:<br />

A. Wireways<br />

2.00 PRODUCT<br />

2.01 MATERIALS<br />

A. WIREWAY: Provide as manufactured by Hoffman or equal.<br />

B. WIREWAY ENCLOSURES, SUPPORTS AND ASSOCIATED FITTINGS: NEMA 1 (metallic)<br />

for Air Conditioned spaces, NEMA 12 for ventilated areas, NEMA 3R for exterior locations <strong>and</strong><br />

NEMA 4X, 304 stainless steel for hazardous/corrosive areas, lay-in wireway, continuously<br />

welded seams, oil resistant gasket. Hoffman Lay-In-Type wireway or equal. Factory ANSI 61<br />

gray finish for NEMA 1.<br />

2.02 FABRICATIONS<br />

A. WIREWAYS: Complete wireway system with enclosures, supports, <strong>and</strong> associated fittings,<br />

having the form <strong>and</strong> dimension suited to the application, <strong>and</strong> as manufactured by Hoffman or<br />

approved equal.<br />

3.00 EXECUTION<br />

3.01 INSTALLATION<br />

A. Provide systems of wireways of sufficient size where indicated.<br />

B. Size wireway cross-sectional area <strong>and</strong> length based upon conductor fill <strong>and</strong> equipment served<br />

as required by NEC <strong>and</strong> local codes.<br />

C. Install types based on environmental conditions to which exposed.<br />

END OF SECTION<br />

Wireways 26 05 33.02-1<br />

DRP09328