26 50 00 LIGHTING<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install light fixtures, complete<br />

with lamps, ballasts <strong>and</strong> other incidentals. Electrical work shall be in accordance with Section 26<br />

05 00, COMMON WORK RESULTS FOR ELECTRICAL.<br />

1.02 QUALITY ASSURANCE<br />

A. ACCEPTABLE MANUFACTURERS<br />

Lamps shall comply with the specifications <strong>and</strong> shall be by the following Manufacturers:<br />

1. General Electric<br />

2. Sylvania<br />

1.03 SUBMITTALS<br />

A. Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include:<br />

1. Product data sheets<br />

2. Performance curves for light fixtures<br />

1.04 DELIVERY AND STORAGE<br />

Ship light fixtures inside protective cartons <strong>and</strong> keep packaged until installed. Deliver lamps to the<br />

job site in the original packing cases <strong>and</strong> sleeves.<br />

1.05 JOB CONDITIONS<br />

A. Provide cold weather ballasts in fixtures which are subject to temperatures below 32 degrees<br />

F.<br />

B. Provide special mounting, enclosures <strong>and</strong> fire-safing, as required by the authorities having<br />

jurisdiction so that the integrity of the U.L. listed ceiling assembles is maintained.<br />

C. Provide U.L. labels where fixtures are subject to moisture. Provide DL or WL label on fixtures<br />

required for the location.<br />

2.00 PRODUCTS<br />

2.01 MATERIALS<br />

A. PLASTIC LENS: Lens for fluorescent fixtures shall be virgin acrylic with a minimum thickness<br />

of 0.125".<br />

B. PHOTOCELL: Fully adjustable from two (2) to 50' c<strong>and</strong>les with SPST contacts; rated 1500<br />

watts at 120 VAC. Cells shall have a built in time delay of five (5) seconds.<br />

C. BALLASTS: Ballast for fluorescent lamps shall be high power factor, dual protected, Class P,<br />

one (1) or two (2) lamps as required, unless otherwise specified on the plans; manufactured<br />

in accordance with CBM st<strong>and</strong>ards, ETL certified, U.L. approved, <strong>and</strong> sound rated "A";<br />

protected by a built-in, resetting, thermal protector. Ballasts for high intensity discharge lamps<br />

shall be high power factor, potted <strong>and</strong> encapsulated. The starting current shall not exceed the<br />

running current. Ballast shall be compatible in design to the specified lamps. Fluorescent<br />

ballasts shall be manufactured by Advance <strong>and</strong> by the manufacturer of the light fixture for Hi-<br />

Intensity ballasts.<br />

Lighting 26 50 00-1<br />