26 05 33.04 PULL AND JUNCTION BOXES FOR ELECTRICAL SYSTEMS<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install pull <strong>and</strong> junction boxes.<br />

The CONTRACTOR shall be responsible for sizing all pull boxes <strong>and</strong> junction boxes per the<br />

National Electrical Code (NEC) Article 314 <strong>and</strong> all other relevant sections of the NEC. Electrical<br />

work shall be in accordance with Section 26 05 00, COMMON WORK RESULTS FOR<br />

ELECTRICAL.<br />

1.02 QUALITY ASSURANCE - ACCEPTABLE MANUFACTURERS<br />

A. Appleton<br />

B. Bryant<br />

C. Crouse Hinds<br />

D. Hoffman<br />

E. Hubbell<br />

F. O Z Gedney<br />

G. Raco<br />

H. Rob Roy<br />

1.03 SUBMITTALS<br />

Submittals shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include the<br />

following shop drawings:<br />

A. Pull <strong>and</strong> Junction Boxes<br />

1.04 STANDARDS<br />

The applicable provisions of the following st<strong>and</strong>ards shall apply as if written here in their entirety:<br />

NEMA 250<br />

ANSI/NEMA OS 1<br />

NEC<br />

Enclosure for Electrical Equipment (1000 volts maximum)<br />

Sheet steel Outlet Boxes, Device Boxes, Covers <strong>and</strong> Box Supports<br />

National Electrical Code<br />

2.00 PRODUCTS<br />

2.01 MATERIALS<br />

A. GENERAL: Exposed wall recessed pull <strong>and</strong> junction boxes shall be NEMA 1 steel for Air<br />

Conditioned spaces, NEMA 12 steel for ventilated areas, NEMA 3R for exterior locations <strong>and</strong><br />

NEMA 4X, 304 stainless steel for corrosive areas. Exposed pull boxes or junction boxes<br />

installed outdoors, per NEMA 250 shall be weatherproof <strong>and</strong> shall be provided with watertight<br />

gasketed covers fastened with stainless steel screws <strong>and</strong> be steel. All hardware shall be<br />

steel. Boxes shall be provided with integral mounting lugs.<br />

B. NEMA 1 (metallic) for Air Conditioned spaces, NEMA 12 for ventilated areas, NEMA 3R for<br />

exterior locations <strong>and</strong> NEMA 4X, 304 stainless steel for corrosive areas.<br />

Pull <strong>and</strong> Junction Boxes for Electrical Systems 26 05 33.04-1<br />

DRP09328