D. CONTROL POWER: Control power shall be 120 VAC from a control transformer located in<br />

each combination starter. Extra control transformer VA capacity shall be furnished for powering<br />

the motor space heater in the motor which the combination starter serves. This extra VA<br />

capacity shall be in addition to the VA required for the other control components powered by<br />

the control transformer. The following is the amount of extra VA capacity which shall be furnished:<br />

COMBINATION<br />

NEMA SIZE<br />

CONTROL TRANSFORMER<br />

EXTRA VA CAPACITY<br />

size 1 100<br />

size 2 200<br />

size 3 300<br />

size 4 500<br />

size 5 750<br />

size 6 1000<br />

This extra VA capacity shall be furnished in each combination starter regardless of where the<br />

motor space heater received its power <strong>and</strong> regardless of whether the motor has a space<br />

heater or not.<br />

E. INTERRUPTING RATING: Both circuit breakers <strong>and</strong> combination starters as complete units<br />

shall be rated for 42,000 Amps Interrupting Capacity (AIC).<br />

F. ENCLOSURES: NEMA 12, 14 gauge steel for interior locations <strong>and</strong> NEMA 4X, 304 stainless<br />

steel for all other locations.<br />

1.07 COORDINATION<br />

A. Coordinate layout <strong>and</strong> installation of enclosed controllers with other construction including<br />

conduit, piping, equipment, <strong>and</strong> adjacent surfaces. Maintain required workspace clearances<br />

<strong>and</strong> required clearances for equipment access doors <strong>and</strong> panels.<br />

B. Coordinate sizes <strong>and</strong> locations of concrete bases with actual equipment provided. Cast anchor-bolt<br />

inserts into bases.<br />

C. Coordinate installation of roof curbs, equipment supports, <strong>and</strong> roof penetrations.<br />

1.08 SPARE PARTS<br />

A. Furnish spare parts that match products installed <strong>and</strong> that are packaged with protective covering<br />

for storage <strong>and</strong> identified with labels describing contents.<br />

2.00 PRODUCTS<br />

1. Control Power Fuses: Equal to 10 percent of quantity installed for each size <strong>and</strong> type,<br />

but no fewer than two of each size <strong>and</strong> type.<br />

2. Indicating Lights: One of each type <strong>and</strong> color installed.<br />

2.01 COMBINATION STARTER<br />

A. The combination starter shall include a motor circuit protector (MCP) type circuit breaker or a<br />

thermal magnetic type circuit breaker as indicated on the Plans. MCP's shall be magnetic trip<br />

only with adjustable magnetic trip limited to 1300% of motor nameplate full load current to<br />

comply with NEC requirements. Devices shown on the schematic <strong>and</strong> not specifically designated<br />

as being elsewhere shall be installed inside the combination starter.<br />

Enclosed Controllers 26 29 13 - 3<br />

DRP09328