F. RUBBER TAPE: Scotch 2210.<br />

G. ARC PROOFING TAPE: 3M “Scotch 77 Fire <strong>and</strong> Electric Arc Proofing Tape”. Medium<br />

voltage cable shall be fireproofed in all manholes <strong>and</strong> h<strong>and</strong>holes. Fireproofing shall be done<br />

with a half-lapped layer of arc proofing tape, anchored at each end with a double wrap of 3M<br />

“Scotch 69 Glass Cloth Electrical Tape”.<br />

H. VINYL TAPE: Scotch 88.<br />

I. INSULATING RESIN: Scotch 3576, 3577, or 3578.<br />

J. POWER DISTRIBUTION BLOCKS: Ferraz Shawmut, Ilsco or Allen-Bradley; rated for 600<br />

VAC <strong>and</strong> termination of copper conductors. Individual poles shall be constructed of tin plated<br />

aluminum <strong>and</strong> mounted on an insulating base.<br />

3.00 EXECUTION<br />

3.01 INSTALLATION<br />

A. For No. 10 <strong>and</strong> smaller, connect conductors with a twist-on spring wirenut. If a splice or tap is<br />

below 3' above the <strong>final</strong> grade, fill the spring connectors with an electrical insulating resin so<br />

that conductor <strong>and</strong> spring materials are encapsulated by the resin. Conductor splices <strong>and</strong><br />

taps inside the MCC, VFDs, panels, etc. shall be on the terminal strips or power distribution<br />

blocks.<br />

B. Splice 600 Volt conductors in junction boxes or at outlets only. All splices are subject to the<br />

Engineer’s approval. Obtain approval from Engineer before installing any splices.<br />

C. For No. 8 <strong>and</strong> larger, connect conductors with a split bolt type of connector or a mechanical,<br />

set screw type connector. Wrap splices <strong>and</strong> taps with a single half-lapped layer or rubber<br />

tape followed by successive layers of vinyl tape until a vinyl tape layer thickness of twice the<br />

original conductor insulation thickness is achieved. If splice or tap is below 3' above the<br />

finished grade, the tape or splice shall have a <strong>final</strong> outer coating or insulating resin.<br />

D. Furnish <strong>and</strong> install power distribution blocks as required for tapping conductors at their load<br />

connection point with conductors of smaller size. Install power distribution blocks with the<br />

number of poles <strong>and</strong> sizes needed for connecting the phase, neutral, <strong>and</strong> ground conductors.<br />

E. Pair shielded cable shield shall be broken at terminal strips only.<br />

F. Application of tape shall be in accordance with the Manufacturer’s recommendations.<br />

END OF SECTION<br />

Wire Connections <strong>and</strong> Devices 26 05 19.01-2<br />