g. Project specific layout of front of controller clearly indentifying the location of all panel<br />

mounted devices.<br />

h. Terminal strip layout clearly showing all field connections.<br />

B. OPERATION AND MAINTENANCE MANUALS:<br />

1. Operation <strong>and</strong> maintenance manuals shall contain the shop drawings, submittals, spare<br />

parts lists, schematics, <strong>and</strong> maintenance procedures.<br />

2. Manuals shall also incorporate appropriate <strong>final</strong> certified shop drawings. Manuals may<br />

be manufacturer's st<strong>and</strong>ard instructions, but shall be supplemented as necessary to<br />

cover any special feature not included in st<strong>and</strong>ard material.<br />

3. Manufacturer's written instructions for testing, adjusting, <strong>and</strong> reprogramming reducedvoltage<br />

solid-state controllers.<br />

C. Load-Current <strong>and</strong> Overload-Relay Heater List: Compile after motors have been installed,<br />

<strong>and</strong> arrange to demonstrate that selection of heaters suits actual motor nameplate full-load<br />

currents.<br />

D. Load-Current <strong>and</strong> List of Settings of Adjustable Overload Relays: Compile after motors have<br />

been installed, <strong>and</strong> arrange to demonstrate that switch settings for motor running overload<br />

protection suit actual motors to be protected.<br />

1.05 DELIVERY, STORAGE, AND HANDLING<br />

A. Store enclosed controllers indoors in clean, dry space with uniform temperature to prevent<br />

condensation. Protect enclosed controllers from exposure to dirt, fumes, water, corrosive<br />

substances, <strong>and</strong> physical damage.<br />

B. If stored in areas subject to weather, cover enclosed controllers to protect them from weather,<br />

dirt, dust, corrosive substances, <strong>and</strong> physical damage. Remove loose packing <strong>and</strong> flammable<br />

materials from inside controllers.<br />

1.06 PROJECT CONDITIONS<br />

A. Environmental Limitations: Rate equipment for continuous operation under the following<br />

conditions unless otherwise indicated:<br />

1. Ambient Temperature: Not less than minus 22 deg F (minus 30 deg C) <strong>and</strong> not<br />

exceeding 122 deg F (50 deg C).<br />

2. Altitude: Not exceeding 3300 feet.<br />

B. HORSEPOWER RATING: Horsepowers as indicated on the Plans are approximate. The<br />

Contractor shall furnish properly sized motor control equipment when actual motor horsepowers<br />

are determined. If actual motor horsepowers differ from the Plans, the Contractor<br />

shall obtain assistance from the Engineer in determining whether or not hardware <strong>and</strong> wiring<br />

changes are necessary. The Contractor shall provide all components <strong>and</strong> wire of the proper<br />

size.<br />

C. OPERATING VOLTAGE: The equipment shall be designed <strong>and</strong> arranged for operation on<br />

208 Volt, 3 phase, 60 Hertz or 120V, 60 Hertz. See plans for more details.<br />

Enclosed Controllers 26 29 13 - 2<br />