26 05 26 GROUNDING & BONDING FOR ELECTRICAL SYSTEMS<br />

1.00 GENERAL<br />

1.01 WORK INCLUDED<br />

Furnish labor, materials, equipment <strong>and</strong> incidentals necessary to install a complete grounding<br />

system in strict accordance with Article 250 of the National Electrical Code (NEC) as shown on<br />

the drawings or as specified herein. Electrical work shall be in accordance with Section 26 05 00,<br />

COMMON WORK RESULTS FOR ELECTRICAL.<br />

1.02 SUBMITTALS<br />

Submittal shall be in accordance with Section 01 33 00, SUBMITTALS <strong>and</strong> shall include:<br />

A. Grounding materials, equipment <strong>and</strong> processes.<br />

B. Product Data: For each type of product supplied.<br />

C. Field quality-control test reports.<br />

1.03 QUALITY ASSURANCE<br />

A. Electrical Components, Devices, <strong>and</strong> Accessories: Listed <strong>and</strong> labeled as defined in NFPA 70,<br />

Article 100, by a testing agency acceptable to authorities having jurisdiction, <strong>and</strong> marked for<br />

intended use.<br />

B. Comply with UL 467 for grounding <strong>and</strong> bonding materials <strong>and</strong> equipment.<br />

1.04 JOB CONDITIONS<br />

Measure the ground grid resistance with the earth test megger <strong>and</strong> install additional ground rods<br />

<strong>and</strong> conductors as required until the resistance to the ground conforms to National Electrical Code<br />

requirements. Ground resistance measurement shall not exceed 5 ohms. Add ground rods as<br />

required to bring resistance to 5 ohms <strong>and</strong> connect to grounding system.<br />

2.00 PRODUCTS<br />

2.01 MATERIALS<br />

A. GROUND RODS: Copper-clad steel, having a diameter of 3/4" <strong>and</strong> a minimum length of 10'.<br />

B. GROUND CABLES: Str<strong>and</strong>ed, bare tinned copper of 98% conductivity <strong>and</strong> as specified in<br />

Section 26 05 19, LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES.<br />

C. CONDUIT GROUND FITTINGS: Fittings for bonding ground cable to the conduit shall be FCI<br />

Burndy Corp., type NE or Thomas & Betts No. 3951 series.<br />

D. GROUND ROD BOXES: Precast Box with cast iron lid. Lid shall read “ground rod” on lid.<br />

Brooks Precast Model. “3-RT” or approved equal. Ground rod boxes located in driveway<br />

areas shall have an AASHTO HS-20 rating.<br />

E. EXOTHERMIC WELDING PROCESS: CADWELD MATERIALS – as manufactured by<br />

ERICO products or approved equal.<br />

Grounding & Bonding for Electrical Systems 26 05 26-1<br />