13 85 10 FIRE SPRINKLER MONITORING SYSTEM<br />

1.00 GENERAL<br />

1.01 SUMMARY<br />

A. This Section includes fire sprinkler monitoring system with manual station, detectors, notification<br />

appliances, signal equipment, controls, <strong>and</strong> devices. The system, accessories, <strong>and</strong> functions<br />

shall be configured to comply with the drawings, specifications, <strong>and</strong> all related codes<br />

<strong>and</strong> st<strong>and</strong>ards including but not limited to those listed <strong>and</strong> described in Section 1.02<br />

DEFINITIONS, CODES, AND STANDARDS.<br />

B. Occupancy classification for this building is:<br />

1. Group “B” – Office/Storage Areas.<br />

2. Group “H” – Fertilizer/Chemical Room.<br />

C. Provide a noncoded, analog addressable system; multiplexed signal transmission dedicated<br />

to fire alarm service only.<br />

1.02 DEFINITIONS, CODES, AND STANDARDS<br />

A. International Fire Code, 2006 Edition.<br />

B. International Mechanical Code, 2006 Edition.<br />

C. National Electrical code, 2005 Edition.<br />

D. City of Dallas amendments <strong>and</strong> ordinances.<br />

E. American with Disabilities Act (ADA), latest Edition.<br />

F. Texas Accessibility St<strong>and</strong>ards (TAS).<br />

G. AHJ: Authority Having Jurisdiction.<br />

H. FACP: Fire alarm control panel.<br />

I. LED: Light-emitting diode.<br />

J. NICET: National Institute for Certification in Engineering Technologies.<br />

K. NFPA 72: National Fire Alarm Code, latest Edition.<br />

L. NFPA 13: National Sprinkler Code.<br />

M. Class “A”: Term as defined in NFPA 72.<br />

N. Definitions in NFPA 72 apply to fire alarm terms used in this Section.<br />

1.03 SYSTEM DESCRIPTION<br />

A. General: Provide fire alarm control panel, devices, <strong>and</strong> associated conduit/wiring etc as specified<br />

to serve the new Parks <strong>and</strong> Recreation Facility. All fire alarm wiring shall be in metal<br />

conduit. Program <strong>and</strong> test the <strong>final</strong> installation in accordance with all applicable codes <strong>and</strong><br />

ordinances. System shall be monitored by remote alarm receiving station. Obtain AHJ’s approval<br />

of finished installation.<br />

B. Performance Requirements:<br />

1. Comply with NFPA 72.<br />

2. Fire alarm signal initiation shall be by one or more of the following devices:<br />

a. Manual stations.<br />

b. Smoke detectors.<br />

c. Automatic sprinkler system water flow.<br />

Fire Alarm <strong>and</strong> Detection System 13 85 10-1<br />