2.00 PRODUCTS<br />

2.01 MANUFACTURED PRODUCTS<br />

A. WALL SWITCHES: For general use, totally enclosed industrial type, specification grade,<br />

rated for 120/277 VAC <strong>and</strong> 20 amps. Approved wire connection to switches shall consist of<br />

inserting wire into back wiring hole <strong>and</strong> tightening terminal screw until wire is tightly griped by<br />

clamping mechanism inside switch body. Side wiring shall not be allowed. Switches installed<br />

in hazardous areas shall be explosion proof type in accordance with the NEC.<br />

B. MOTOR RATED SWITCHES: HP rated switches approved for motor control or disconnect<br />

service when controlling or disconnecting motor loads in excess of 1/4 HP; 20 amp switches<br />

for loads exceeding 10 amps.<br />

C. WEATHERPROOF SWITCHES: Fitted with a single switch as specified, <strong>and</strong> weatherproof<br />

cover with spring door cover; gray in color for all areas.<br />

D. RECEPTACLES: For general use shall be U.L. approved, hospital grade heavy duty duplex<br />

grounding type 20 ampere 125 volt heavy duty phosphor bronze contacts. Terminal screws<br />

shall be large head, deep slotted #8-32 brass, backed out, staked <strong>and</strong> spring latched for rapid<br />

wiring, color coded for polarity identification, <strong>and</strong> shall accept up to 10 AWG wire. Approved<br />

wire connection to receptacles shall consist of inserting wire into back wiring hole <strong>and</strong><br />

tightening terminal screw until wire is tightly gripped by clamping mechanism inside the<br />

receptacle body. Side wiring shall not be allowed.<br />

E. GROUND FAULT CIRCUIT INTERRUPTING, INDOOR: GFCI receptacle shall include visible<br />

indication of ground fault condition. Feed-through feature shall not be used. Install GFCI<br />

device at each location indicated. GFCI circuit breaker shall not be permitted.<br />

F. WEATHERPROOF RECEPTACLES:<br />

1. Weatherproof receptacles shall be hospital grade, 20 ampere, 125 volt <strong>and</strong> shall be listed<br />

as weather resistant type in accordance with the National Electrical Code <strong>and</strong> shall<br />

include a weatherproof device cover.<br />

a. Weatherproof Duplex Receptacle: Provide GFCI duplex receptacle with weatherproof<br />

cover.<br />

b. Weatherproof Single Receptacle: Provide a cast box fitted with a single receptacle<br />

<strong>and</strong> threaded cap with a weatherproof cover.<br />

2. Weatherproof device covers shall have a NEMA 3R rating while receptacle is in use rating<br />

with die cast aluminum construction as manufactured by Thomas & Betts Model No.<br />

CKMUV or approved equal.<br />

G. WEATHER RESISTANT RECEPTACLES: Weather resistant receptacles shall be listed as<br />

weather resistant type in accordance with the National Electrical Code.<br />

H. SWITCH AND RECEPTACLE COVER PLATES: The cover plate color shall be gray for all<br />

areas, unless otherwise indicated or required by the NEC. Screw heads shall have color to<br />

match plate. Non-weatherproof; 302/304 stainless steel. Provide telephone cover plates<br />

which are the same as above, except with a single bushed pole for the telephone cable.<br />

3.00 EXECUTION<br />

3.01 INSTALLATION<br />

Wiring Devices 26 27 26-2<br />