11.07.2015 Views

12th International Symposium on District Heating and Cooling

12th International Symposium on District Heating and Cooling

12th International Symposium on District Heating and Cooling

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

The <str<strong>on</strong>g>12th</str<strong>on</strong>g> <str<strong>on</strong>g>Internati<strong>on</strong>al</str<strong>on</strong>g> <str<strong>on</strong>g>Symposium</str<strong>on</strong>g> <strong>on</strong> <strong>District</strong> <strong>Heating</strong> <strong>and</strong> <strong>Cooling</strong>,September 5 th to September 7 th , 2010, Tallinn, Est<strong>on</strong>iato decrease, <strong>and</strong> thereby also the temperature drop<strong>and</strong> heat supply, to be detained at the same level.A test is started by keeping the CV locked for tenminutes. This leaves enough time for the HEX tostabilise. The new level of the difference between theprimary <strong>and</strong> sec<strong>on</strong>dary return temperatures becamestable already after about two minutes in the testedobjects. The CV was maintained locked for tenminutes, which should be sufficient even for very lowflows <strong>and</strong> most types of HEXs. Subsequently, thec<strong>on</strong>trol was resumed in order to ensure a c<strong>on</strong>stanttemperature drop <strong>on</strong> the sec<strong>on</strong>dary side.The temperature drop was c<strong>on</strong>trolled by verifying thecurrent temperature drop, e.g., every five minutes, <strong>and</strong>comparing it with the desired temperature drop, i.e., thetemperature that was observed when the CV waslocked. If the difference exceeded a certain value,0.2 °C has been used so far, the set-point for thesupply temperature was updated according toT setpoint = T s,r + T setpoint .Fig. 3 displays a performed test: At 1:00 a.m., the CVwas locked <strong>and</strong> the radiator flow rate was reduced from0.59 to 0.36 l/s with the result that the sec<strong>on</strong>darysupply temperature rose from 40 to 44 °C. After tenminutes, the temperature drop in the radiator circuitwas automatically c<strong>on</strong>trolled (in this case, thetemperature drop was stable <strong>and</strong> it took more than 15minutes before the CV opening degree requiredadjustment). After ninety minutes, the sec<strong>on</strong>d flowreducti<strong>on</strong> was carried out, to 0.24 l/s, <strong>and</strong> thesec<strong>on</strong>dary supply temperature increased to about48 °C.The total primary return temperature varied to arelatively large extent, partly because of tappings ofdomestic hot water (DHW), but also due to the DHWc<strong>on</strong>trol in this substati<strong>on</strong> being very unstable when notappings were made. However, the return temperaturefrom the radiator HEX was of interest for the tests. Inthis object, the difference between the primary <strong>and</strong>sec<strong>on</strong>dary return temperatures was very small, <strong>and</strong>even for a low radiator flow, the grädigkeit was below<strong>on</strong>e degree. One can see from the figure that the returntemperature had fallen from just under 32 °C to slightlyover 28 °C during the test. This resulted in, for acurrent outdoor temperature of 8 °C, the set-point forthe sec<strong>on</strong>dary supply temperature being changed from40 to 48 °C while the flow should be reduced from 0.59to 0.24 l/s.Temperature [ C]Flow [l/s]%Heat supply [kW]8070605040302010000:30 01:00 01:30 02:00 02:30 03:00 03:30 04:00Time2010010.750.50.250604020CV,heatCV,DHW000:30 01:00 01:30 02:00 02:30 03:00 03:30 04:00TimeT p,sT s,rT p,r,radT p,r,totT s,rT sT oT o,dampFig. 3 Results from a test. The flow was reduced at 1:00<strong>and</strong> 2:30. The top graph shows temperatures in thesubstati<strong>on</strong>, the next graph presents the valve positi<strong>on</strong> forheat <strong>and</strong> DHW, <strong>and</strong> the last two display the primary(including DHW) <strong>and</strong> sec<strong>on</strong>dary flow <strong>and</strong> the primary(including DHW) <strong>and</strong> sec<strong>on</strong>dary heat supply, respectively.An interesting aspect of this test was that the primarysupply temperature fluctuated a lot. Since thesec<strong>on</strong>dary temperature drop was kept c<strong>on</strong>stant, it hadno impact <strong>on</strong> the outcome of the test. One can see thatthe CV generally dem<strong>on</strong>strated a lower opening degreelater in the night, as opposed to before 1:00, when theprimary supply temperature increased. Without the Tc<strong>on</strong>trol, the heat supply would have been too highduring the last part of the test.The radiator flow was altered by changing the set-pointfor the pump speed, expressed as a percentage of themaximum speed. It has been found that two flowalterati<strong>on</strong>s of ninety minutes each are suitable per test,as this would allow the sec<strong>on</strong>dary return temperature tostabilise even at very low flows. The first test for anyoutdoor temperature, as was the case in Fig. 3, meansthat starting c<strong>on</strong>diti<strong>on</strong>s include the original c<strong>on</strong>trolcurve <strong>and</strong> flow rate. It is then desirable to perform twofairly large flow reducti<strong>on</strong>s since, according to thetheoretical calculati<strong>on</strong>s, <strong>on</strong>e can expect to find anoptimum at a relatively low flow. If, however, the flow isalready <strong>on</strong> a low level, it is reas<strong>on</strong>able to attempt <strong>on</strong>eslightly higher <strong>and</strong> <strong>on</strong>e slightly lower flow rate. Thealgorithm for the adaptive c<strong>on</strong>trol is illustrated by theflow chart in Fig. 4.m pQ pm sQ sGr210

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!