SS Single shot timer<br />

Expression<br />

Input ⎯[ A SS B ]⎯ Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is changed from OFF to ON, the output and the timer device corresponding to the<br />

timer register B are set to ON, and timer updating for B is started. The elapsed time is stored in B.<br />

When the specified time by A has elapsed after the input came ON, the output and the timer device<br />

are turned OFF. (Timer updating is stopped)<br />

The available data range for operand A is 0 to 32767.<br />

Execution condition<br />

Input Operation Output<br />

OFF Elapsed time < preset time (timer is updating) ON<br />

Elapsed time ≥ preset time (timer is not updating) OFF<br />

ON Elapsed time < preset time (timer is updating) ON<br />

Elapsed time ≥ preset time (timer is not updating) OFF<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Preset time √ √ √ √ √ √ √ √ √ √ 0 - 32767<br />

B Elapsed time √<br />

Example<br />

Y021 (and the timer device T.003) is turned OFF 1 second after X000 came ON.<br />

X000<br />

Preset value<br />

T003<br />

T.003<br />

Y021<br />

Preset time (1 s) Preset time (1 s)<br />

Note<br />

• Time is set in 10 ms units for;<br />

<strong>T1</strong>: T000 to T031 (0 to 327.67 s)<br />

<strong>T1</strong>S: T000 to T063 (0 to 327.67 s)<br />

• Time is set in 100 ms units for;<br />

<strong>T1</strong>: T032 to T063 (0 to 3276.7 s)<br />

<strong>T1</strong>S: T064 to T255 (0 to 3276.7 s)<br />

• Multiple timer instructions (TON, TOF or<br />

SS) with the same timer register are not<br />

allowed.<br />

Basic Hardware and Function 131<br />