7. Instructions<br />

FUN 144 STIZ Step sequence initialize<br />

Expression<br />

Input −[ STIZ (n) A ]− Output<br />

Function<br />

When the input is ON, n devices starting with A are reset to OFF, and A is set to ON.<br />

This instruction is used to initialize a series of step sequence. The step sequence is useful to<br />

describe a sequential operation.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution at the rising edge of the input ON<br />

212 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

n Size of step<br />

sequence<br />

1 - 64<br />

A Start device √<br />

Example<br />

When R020 is changed from OFF to ON, R400 is set to ON and subsequent 9 devices (R401<br />

to R409) are reset to OFF.<br />

This instruction initializes a series of step sequence, 10 devices starting with R400.<br />

R409 R408 R407 R406 R405 R404 R403 R402 R401 R400<br />

OFF OFF OFF OFF OFF OFF OFF OFF OFF ON<br />

10 devices starting with R400<br />

Note<br />

• The STIZ instruction is used together with STIN (FUN 145) and STOT (FUN 146) instructions to<br />

configure the step sequence.<br />

• The STIZ instruction is executed only when the input is changed from OFF to ON.<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net