7. Instructions<br />

FUN 146 STOT Step sequence output<br />

Expression<br />

Input −[ STOT A ]−⎢<br />

214 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function<br />

When the input is ON, the device A is set to ON and the devices of STIN instructions on the same<br />

rung are reset to OFF.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution -<br />

ON Execution -<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Step device √<br />

Example<br />

See example on STIN (FUN 145) instruction.<br />

Note<br />

• The STIZ, STIN and STOT instructions are used together to configure the step sequence.<br />

• Two or more STOT instructions can be placed on one rung to perform simultaneous sequences.<br />

• Two or more STIN instructions can be placed on one rung in parallel or in series to perform loop<br />

or convergence of sequences. (Max. 11 STIN instructions on one rung)<br />

• To perform the conditional branch (sequence selection), separate the rungs as follows.<br />

This limitation is applied to <strong>T1</strong> version 1.00 only.<br />

[ STIN A ] | | [ STOT B ] [ STIN A ] | | [ STOT B ]<br />

| | [ STOT C ] [ STIN A ] | | [ STOT C ]<br />

Not allowed Available<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net