6F3B0253<br />

1. System Configuration<br />

Computer link mode<br />

T-series computer link protocol can be used in this mode. A maximum of 32 <strong>T1</strong>-<strong>16S</strong>s<br />

can be connected to a master computer.<br />

By using this mode, all the <strong>T1</strong>-<strong>16S</strong>’s data can be accessed by a master computer.<br />

The T-series <strong>PLC</strong> programming software (T-PDS) can also be used in this<br />

configuration.<br />

<strong>T1</strong>-<strong>16S</strong><br />

Master Computer<br />

RS-485 (1 km max.)<br />

<strong>T1</strong>-<strong>16S</strong> <strong>T1</strong>-<strong>16S</strong><br />

Max. 32 <strong>T1</strong>-<strong>16S</strong>s<br />

<strong>T1</strong>-<strong>16S</strong><br />

Data link mode<br />

Two <strong>PLC</strong>s (any combination of <strong>T1</strong>-<strong>16S</strong>, T2E or T2N) can be directly linked together.<br />

This direct link is inexpensive, easily configured and requires no special<br />

programming. Data registers D0000 to D0031 are used for the data transfer.<br />

<strong>T1</strong>-<strong>16S</strong><br />

Station No. 1<br />

D0000<br />

D0015<br />

D0016<br />

D0031<br />

RS-485 (1 km max.)<br />

<strong>T1</strong>S<br />

Station No. 2<br />

D0000<br />

D0015<br />

D0016<br />

D0031<br />

Basic Hardware and Function 29<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net<br />