Read command mode (Mode 2) ><br />

6F3B0253<br />

7. Instructions<br />

When the instruction input comes ON with the operand B+1 is 2, the Read command mode<br />

(mode 2) is selected. In this mode, the <strong>T1</strong>-<strong>16S</strong> sends the user specified Read command to the<br />

Inverter specified by the operand B, and repeats.<br />

Repeat<br />

Sends the specified command to #n Inverter<br />

Receives the response and stores the data into the register<br />

The target Inverter number #n is specified by the operand B.<br />

The scan execution status and the Inverter communication status are stored in the operand<br />

B+2 to B+7.<br />

The command setting register and the response data storing register is indirectly specified by<br />

the operand A and A+1.<br />

When the instruction input is reset to OFF, the operation is stopped after receiving the<br />

response from the Inverter.<br />

Example<br />

Data table designation Parameter & status RS-485 port<br />

D1000 4 RW200 3 D1010 H0030 (fixed)<br />

D1001 3000 RW201 2 (mode 2) D1011 0 (fixed)<br />

RW202 Execution status<br />

RW203 Comm error code<br />

RW204<br />

RW205 Inverter comms<br />

RW206 status map<br />

RW207<br />

When the data for each operand are set as above, the following operation condition is specified.<br />

• RW200=3 ⇒ The target Inverter number is 3. Therefore <strong>T1</strong>-<strong>16S</strong> communicates with #3 Inverter.<br />

• D1000=4 & D1001=3000 ⇒ D3000 is specified as the command setting register and D3001 is specified<br />

as the response data storing register.<br />

Data table:<br />

Register Data contents Signal direction<br />

D3000 Command code<br />

D3001 Response data ← Read<br />

Example operation:<br />

For example, to read the output current from the #3 Inverter, set the command code HFE03 into<br />

D3000. Then the response data is stored in D3001. If the response data is 1915, it means 19.15 %.<br />

For the command code and the data format of the response, refer to your Inverter manual.<br />

Basic Hardware and Function 251<br />