FUN 064 TEST Bit test<br />

Expression<br />

Input −[ A TEST B ]− Output<br />

6F3B0253<br />

7. Instructions<br />

Function<br />

When the input is ON, this instruction finds logical AND of A and B. Then if the result is not 0, sets<br />

the output to ON.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution When the result is not 0 ON<br />

When the result is 0 OFF<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

B Test data √ √ √ √ √ √ √ √ √ √ √ √<br />

Example<br />

Logical AND operation is executed for the data of RW07 and the constant data H0FFF, and if<br />

the result is not 0, R00A is turned ON. (R00A is turned ON when any device from R070 to<br />

R07B is ON.)<br />

If the data of RW07 is H4008, R00A is turned ON.<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

RW07 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0<br />

4 0 0 8<br />

AND<br />

Constant 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1<br />

0 F F F<br />

Result is not 0<br />

Result 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 R00A comes ON<br />

Basic Hardware and Function 163<br />