7. Instructions<br />

FUN 190 BCD BCD conversion<br />

Expression<br />

Input −[ A BCD B ]− Output<br />

238 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function<br />

When the input is ON, this instruction converts the binary data of A into BCD, and stores in B. If the<br />

data of A is not in the range of 0 to 9999, the conversion is not executed and the instruction error<br />

flag (ERF = S051) is set to ON.<br />

Execution condition<br />

Input Operation Output ERF<br />

OFF No execution OFF −<br />

ON Normal execution ON −<br />

Binary data error OFF Set<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source<br />

√ √ √ √ √ √ √ √ √ √ 0 - 9999<br />

(Binary)<br />

B Destination<br />

(BCD)<br />

Example<br />

√ √ √ √ √ √ √ √ √<br />

When R019 is ON, the data of D0211 is converted into 4-digit BCD, and the result is stored in<br />

RW22.<br />

For example, if D0211 is 5432, the BCD data H5432 is stored in RW22.<br />

D0211 Binary to BCD RW22<br />

5432 H5432<br />

Note<br />

• If the data of A is smaller than 0 or greater than 9999, the conversion is not executed and the<br />

instruction error flag (ERF = S051) is set to ON.<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net