7. Instructions<br />

FUN 114 SET Device/register set<br />

Expression<br />

Input −[ SET A ]− Output<br />

196 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function<br />

When the input is ON, the device A is set to ON if A is a device, or the data HFFFF is stored in the<br />

register A if A is a register.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

Operand<br />

Name Device Register Constant Index<br />

A Device or<br />

register<br />

Example 1 (device set)<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

√ √ √ √ √ √ √ √ √ √ √ √<br />

When R010 is ON, R025 is set to ON. The state of R025 is remained even if R010 comes<br />

OFF.<br />

Example 2 (register set)<br />

When R010 is ON, the data HFFFF is stored in RW20. (R200 to R20F are set to ON)<br />

The state of RW20 is remained even if R010 comes OFF.<br />