2. Specifications<br />

2.3 I/O specifications<br />

• Input specifications<br />

Item Specifications<br />

Input type DC input, current source/sink<br />

Number of input points 8 points (8 points/common)<br />

Rated input voltage 24Vdc, +10/-15 %<br />

Rated input current 7mA (at 24Vdc)<br />

Min. ON voltage 15Vdc<br />

Max. OFF voltage 5Vdc<br />

ON delay time 0 to 15ms *1<br />

OFF delay time 0 to 15ms *1<br />

Input signal display LED display for all points, lit at ON, internal logic<br />

side<br />

External connection Removable terminal block, M3<br />

Withstand voltage 1500Vac, 1 minute<br />

(between internal and external circuits)<br />

Internal circuit<br />

LED<br />

42 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

0<br />

7<br />

C<br />

*1: User can change the input ON/OFF delay time of the DC input.<br />

The setting range is 0 to 15ms. (Default value = 10ms) Refer to section 8.2.<br />

Internal circuit<br />

6F3B0253<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net