8. Special I/O Functions<br />

8.5 Analog setting function<br />

Function<br />

The value of the analog setting adjuster is converted into a digital value (0 to 1000)<br />

and stored in the SW register. 2 adjusters are provided. (V0 and V1)<br />

The SW register data can be used as timer presets or any parameters for function<br />

instructions.<br />

Related registers<br />

Function Register Remarks<br />

Adjuster V0 SW30 Data range: 0 to 1000<br />

Adjuster V1 SW31<br />

Operation<br />

Decrease Increase Decrease Increase<br />

Sample program<br />

270 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

V0 V1<br />

SW30 (0 to 1000) SW31 (0 to 1000)<br />

The above example is a simple flicker circuit of Y020. In this example, the ON/OFF<br />

interval of Y020 can be controlled by the adjuster V0.<br />

6F3B0253<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net