4. Installation and Wiring<br />

4.4 Grounding<br />

! CAUTION<br />

58 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

1. Turn off power before wiring to minimize the risk of electrical shock.<br />

6F3B0253<br />

2. Operation without grounding may cause electrical shock or malfunction.<br />

Connect the ground terminal on the <strong>T1</strong>-<strong>16S</strong> to the system ground.<br />

The optimum method for grounding electronic equipment is to ground it separately<br />

from other high-power systems, and to ground more than one units of electronic<br />

equipment with a single-point ground.<br />

Although the <strong>T1</strong>-<strong>16S</strong> has noise immunity to be used in industrial operating conditions,<br />

grounding is important for safety and reliability.<br />

Check the grounding against the following criteria.<br />

1. The <strong>T1</strong>-<strong>16S</strong> must not become a path for a ground current. A high-frequency current<br />

is particularly harmful.<br />

2. Equalize the ground potentials when the expansion rack or unit is connected.<br />

Ground the <strong>T1</strong>-<strong>16S</strong> and the expansion rack or unit at a single point.<br />

3. Do not connect the ground of the <strong>T1</strong>-<strong>16S</strong> to that of high-power systems.<br />

4. Do not use a ground that has unstable impedance, such as painted screws, or<br />

ground subject to vibration.<br />

The grounding marked terminal (see below) is provided on the <strong>T1</strong>-<strong>16S</strong> basic unit for<br />

grounding purpose.<br />

In case of the expansion rack is connected to the <strong>T1</strong>-<strong>16S</strong>, the rack mounting screw is<br />

used for this purpose.<br />

System ground<br />

<strong>T1</strong>-<strong>16S</strong><br />

Mounting panel<br />

• 1.25mm 2 (16 AWG) wire should be used to connect the <strong>T1</strong>-<strong>16S</strong> and the expansion<br />

rack/unit with the enclosure grounding bus bar.<br />

• 100Ω or less to ground is required.<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net