6F3B0253<br />

6. Programming Information<br />

External input devices (X)<br />

These devices (X) indicate the ON/OFF states of external input signals through the<br />

input circuits. External input devices can be used many times in a program.<br />

External output devices (Y)<br />

The external output devices (Y) store the ON/OFF signals that drive the external<br />

devices through the output circuits. They can be used for coils in a program.<br />

External input registers (XW)<br />

These (XW) are 16-bit registers for storing values, which are received from the input<br />

circuits.<br />

External output registers (YW)<br />

These 16-bit registers (YW) are used for storing values, which are sent to the output<br />

circuits.<br />

Auxiliary relay devices and registers (R/RW)<br />

The auxiliary relay devices (R) are used to store intermediate results of sequences.<br />

The auxiliary relay registers (RW) are used to store temporary results of function<br />

instructions. The data in R/RW cannot be output directly to the output circuits. It is<br />

necessary to move the data to Y/YW.<br />

It is possible to make these registers retentive so that they retain data in the event of a<br />

power failure. See section 5.3.<br />

Timer devices and registers (T./T)<br />

The timer registers (T) are used for storing the elapsed time of timer instructions, the<br />

on-delay (TON), off-delay (TOF) and single-shot (SS) timers.<br />

0.01 s base timers and 0.1 s base timers are provided.<br />

Time base <strong>T1</strong>-<strong>16S</strong><br />

0.01 s T000 to T063<br />

0.1 s T064 to T255<br />

The timer devices (T.) work as the output of the timer instructions.<br />

It is possible to specify the T registers as retentive to retain their data in the event of a<br />

power failure. See section 5.3.<br />