7. Instructions<br />

FUN 024 TINZ Table initialize<br />

Expression<br />

Input −[ A TINZ (n) B ]− Output<br />

Function<br />

When the input is ON, the data of A is stored in n registers starting with B.<br />

The allowable range of the table size n is 1 to 1024 words.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

140 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √<br />

n Table size 1 - 1024<br />

B Start of<br />

destination<br />

√ √ √ √ √ √<br />

Example<br />

When R010 is ON, a constant data (0) is stored in 100 registers starting with D0200 (D0200 to<br />

D0299) and the output is turned ON.<br />

Constant 0 D0200 0<br />

D0201 0<br />

D0202 0 100 registers<br />

D0299 0<br />