7. Instructions<br />

FUN 164 AVE Average value<br />

Expression<br />

Input −[ A AVE (n) B ]− Output<br />

228 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Function<br />

When the input is ON, this instruction calculates the average value of the data stored in the n<br />

registers starting with A, and stores the average value in B. The allowable range of the table size n<br />

is 1 to 64.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Start of table √ √ √ √ √ √ √<br />

n Table size 1 - 64<br />

B Result √ √ √ √ √ √ √ √ √<br />

Example<br />

When R012 is ON, the average value of the data stored in the register table D0200 to D0209<br />

(10 words), and the average value is stored in D0520.<br />

D0200 100<br />

D0201 10000<br />

D0202 -1000<br />

D0203 10<br />

D0204 0 D0520 2900 (Average value)<br />

D0205 200<br />

D0206 -300<br />

D0207 20000<br />

D0208 -30<br />

D0209 20<br />