1. System Configuration<br />

1.8 Real-time data link system<br />

TOSLINE-F10<br />

32 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

TOSLINE-F10 is a high speed data transmission system suited for small points I/O<br />

distribution system. By inserting the TOSLINE-F10 remote module (FR112M), the<br />

<strong>T1</strong>-<strong>16S</strong> can work as a remote station of the TOSLINE-F10 network. On this network,<br />

the <strong>T1</strong>-<strong>16S</strong> sends 1 word data to the master station and receives 1 word data from<br />

the master station.<br />

Item TOSLINE-F10 system specifications<br />

High speed mode Long distance mode<br />

Topology Bus (terminated at both ends)<br />

Transmission distance<br />

(without repeater)<br />

500 m max. (total) 1 km max. (total)<br />

Transmission speed 750 kbps 250 kbps<br />

Scan transmission 512 points (32 words) max.<br />

capacity<br />

Scan cycle 7 ms/32 words 12 ms/32 words<br />

Error checking CRC check<br />

NOTE<br />

Typical data link configuration<br />

The figure below shows the typical data link configuration.<br />

<strong>T1</strong>-<strong>16S</strong><br />

(1) Refer to the separate “<strong>T1</strong> User’s <strong>Manual</strong> − Option Card and I/O<br />

Module −“ for details of the TOSLINE-F10 remote card (FR112).<br />

(2) Refer to the separate TOSLINE-F10 User’s <strong>Manual</strong> for details of<br />

overall TOSLINE-F10 system.<br />

TOSLINE-F10<br />

<strong>T1</strong>-<strong>16S</strong> <strong>T1</strong>-<strong>16S</strong><br />

Operator interface units<br />

Master<br />

computer<br />

T2E<br />

(master)<br />

T2E<br />

(remote)<br />

RI/O<br />

RI/O<br />

RI/O: remote I/O<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net