7. Instructions<br />

FUN 102 D> Double-word greater than<br />

Expression<br />

Input −[ A+1⋅A D> B+1⋅B ]− Output<br />

Function<br />

When the input is ON, the double-word data of A+1⋅A and B+1⋅B are compared, and if A+1⋅A is<br />

greater than B+1⋅B, the output is turned ON.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution A+1⋅A > B+1⋅B ON<br />

A+1⋅A ≤ B+1⋅B OFF<br />

184 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Compared<br />

√ √ √ √ √ √ √ √<br />

data<br />

B Reference<br />

data<br />

Example<br />

√ √ √ √ √ √ √ √<br />

When R010 is ON, the data of D0101⋅D0100 is compared with the constant data 200000, and<br />

if the data of D0101⋅D0100 is greater than 200000, R014 is turned ON.<br />

If the data of D0101⋅D0100 is 250000, the comparison result is true. Consequently, R014 is<br />

turned ON.<br />

D0101⋅D0100 250000 > Constant 200000 R014 is ON<br />

If the data of D0101⋅D0100 is -100, the comparison result is false. Consequently, R014 is<br />

turned OFF.<br />

D0101⋅D0100 -100 ≤ Constant 200000 R014 is OFF<br />

Note<br />

• This instruction deals with the data as double-word integer (-2147483648 to 2147483647).<br />