10.1.4 Input check<br />

6F3B0253<br />

10. Troubleshooting<br />

If the program is running but the external input signal is not read normally, check the<br />

following points:<br />

Is the input status LED If not, check the input voltage at the<br />

changed ON/OFF according <strong>T1</strong>-<strong>16S</strong>’s input terminals.<br />

to the corresponding input If the voltage is not normal, check the input<br />

device operation ? device and the cable.<br />

If the voltage is normal, the <strong>T1</strong>-<strong>16S</strong>’s input<br />

Yes circuit may be faulty.<br />

Connect the programming If the monitored X device state is identical<br />

tool, and monitor the to the state of the input status LED, the<br />

corresponding X device state cause may lie in the user program or in the<br />

in RUN mode environment.<br />

Not normal<br />

Check whether the X device If it is forced, release the force designation<br />

is forced or not then execute the EEPROM write<br />

operation.<br />

Not forced<br />

Check whether the I/O If identical, the <strong>T1</strong>-<strong>16S</strong>’s internal circuit or<br />

allocation table is identical to the input circuit may be faulty.<br />

the actual I/O configuration<br />

Not identical<br />

Execute the automatic I/O If it becomes identical, execute the<br />

allocation, and check whether EEPROM write operation.<br />

the I/O allocation table is now<br />

identical to the actual I/O<br />

configuration<br />

Still not identical<br />

Is the allocation mismatch for If so, the card, module or expansion unit<br />

a specific I/O module? may be faulty. For expansion unit, check<br />

the expansion cable also.<br />

Basic Hardware and Function 285<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net