6. Programming Information<br />

Available address range<br />

Device/register Symbol<br />

<strong>T1</strong>-<strong>16S</strong><br />

Number of points Address range<br />

External input device X Total 512 points X000 - X31F<br />

External output device Y<br />

Y020 - Y31F<br />

External input register XW Total 32 words XW00 - XW31<br />

External output register YW<br />

YW02 - YW31<br />

Auxiliary relay device R 4096 points R000 - R255F<br />

Auxiliary relay register RW 256 words RW000 - RW255<br />

Special device S 1024 points S000 - S63F<br />

Special register SW 64 words SW00 - SW63<br />

Timer device T. 256 points T.000 - T.255<br />

Timer register T 256 words T000 - T255<br />

Counter device C. 256 points C.000 - C.255<br />

Counter register C 256 words C000 - C255<br />

Data register D 4096 words D0000 - D4095<br />

Index register<br />

I 1 word I (no address)<br />

J 1 word J (no address)<br />

K 1 word K (no address)<br />

NOTE<br />

76 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

(1) 1 word = 16 bits<br />

(2) The available data range in each register is -32768 to 32767 (H8000 to<br />

H7FFF) except for the timer and the counter registers.<br />

The data range of the timer register is 0 to 32767. That of the counter<br />

register is 0 to 65535.<br />

(3) Double-word (32 bits) data is available in two consecutive registers.<br />

In this case, lower address register stores the lower 16 bits data.<br />

(MSB) F -------------0 F ------------ 0 (LSB)<br />

D0101 D0100<br />

Upper 16bits Lower 16bits<br />

In this manual, a double-word register is expressed by using ‘⋅’.<br />

For example, D0101⋅D0100.<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net