7. Instructions<br />

FUN 048 AND AND<br />

Expression<br />

Input −[ A AND B → C ]− Output<br />

Function<br />

When the input is ON, this instruction finds logical AND of A and B, and stores the result in C.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

156 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

B Source √ √ √ √ √ √ √ √ √ √ √ √<br />

C AND √ √ √ √ √ √ √ √ √ √<br />

Example<br />

When R012 is ON, logical AND operation is executed for the data of RW12 and the constant<br />

data HFF00, and the result is stored in D0030.<br />

If the data of RW12 is H3456, the result H3400 is stored in D0030.<br />

F E D C B A 9 8 7 6 5 4 3 2 1 0<br />

RW12 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0<br />

3 4 5 6<br />

AND<br />

Constant 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0<br />

F F 0 0<br />

D0030 0 0 1 1 0 1 0 0 0 0 0 0 0 0 0 0<br />

3 4 0 0<br />