10. Troubleshooting<br />

10.1.5 Output check<br />

If the output status monitored on the programming tool is normal but the external<br />

output device (load) is not operated normally, check the following points:<br />

Is the output status LED<br />

changed ON/OFF according<br />

No to the program execution ?<br />

Yes<br />

286 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Check the voltage between If it is the circuit voltage at the output is<br />

the output terminal and its ON, or if it is 0V at the output is OFF with<br />

common terminal. the load ON, the <strong>T1</strong>-<strong>16S</strong>’s output circuit<br />

It should be 0V when the may be faulty.<br />

output is ON, and it should If it is 0V and the load is also OFF, check<br />

be the circuit voltage when the output power and the output cable<br />

the output is OFF. connections.<br />

Normal<br />

If it is not normal, check the output cable<br />

Check the voltage at the load connections.<br />

If it is normal, check the specification of<br />

the load, also check environmental factors.<br />

Check whether the I/O If identical, the <strong>T1</strong>-<strong>16S</strong>’s internal circuit or<br />

allocation table is identical to the output circuit may be faulty.<br />

the actual I/O configuration<br />

Not identical<br />

Execute the automatic I/O If it becomes identical, execute the<br />

allocation, and check whether EEPROM write operation.<br />

the I/O allocation table is now<br />

identical to the actual I/O<br />

configuration<br />

Still not identical<br />

Is the allocation mismatch for If so, the card, module or expansion unit<br />

a specific I/O module? may be faulty. For expansion unit, check<br />

the expansion cable also.<br />