7. Instructions<br />

FUN 018 MOV Data transfer<br />

Expression<br />

Input −[ A MOV B ]− Output<br />

Function<br />

When the input is ON, the data of A is stored in B.<br />

Execution condition<br />

Input Operation Output<br />

OFF No execution OFF<br />

ON Execution ON<br />

136 <strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong><br />

6F3B0253<br />

Operand<br />

Name Device Register Constant Index<br />

X Y R S T. C. XWYWRWSW T C D I J K<br />

A Source √ √ √ √ √ √ √ √ √ √ √ √<br />

B Destination √ √ √ √ √ √ √ √ √ √<br />

Example 1 (constant to register)<br />

When R010 is ON, a constant data (12345) is stored in D0100 and the output is turned ON.<br />

Example 2 (register to register)<br />

When X005 is ON, the data of SW30 is stored in RW45 and the output is turned ON. If SW30<br />

is 500, the data 500 is stored in RW45.<br />

Example 3 (index modification)<br />

When R050 is changed from OFF to ON, the data of RW08 is stored in the index register I and<br />

the data of D(0000+I) is stored in YW10. If RW08 is 300, the data of D0300 is stored in YW10.<br />