4.3 Wiring terminals<br />

! CAUTION<br />

6F3B0253<br />

4. Installation and Wiring<br />

The terminal screw size of the <strong>T1</strong>-<strong>16S</strong> is M3. Use crimp-style terminals of 7mm width<br />

or less useable for M3. The terminal block is not removable (fixed).<br />

NOTE<br />

For input and output signal connections, refer to sections 2.4 and 3.<br />

<strong>T1</strong>-MDR<strong>16S</strong>S .... AC power supply model <strong>T1</strong>-MDR<strong>16S</strong>SD.. DC power supply model<br />

RS-485 (Enhanced model only)<br />

TXA RXA RXB<br />

TXB TRM SG<br />

MDR<strong>16S</strong>S<br />

DC IN<br />

DC OUT<br />

RELAY OUT<br />

L − C 1 3 5 7 Vin 21 23 25 27<br />

N NC + 0 2 4 6 C 20 22 24 26 C<br />

NOTE<br />

1. Turn off power before wiring to minimize the risk of electrical shock.<br />

2. Exposed conductive parts of wire can cause electrical shock. Use<br />

crimp-style terminals with insulating sheath or insulating tape to cover<br />

the conductive parts. Also close the terminal covers securely on the<br />

terminal blocks when wiring has been completed.<br />

3. Turn off power before removing or replacing units, modules, terminal<br />

blocks or wires. Failure to do so can cause electrical shock or damage<br />

to the <strong>T1</strong>-<strong>16S</strong> and related equipment.<br />

RS-485 (Enhanced model only)<br />

TXA RXA RXB<br />

TXB TRM SG<br />

MDR<strong>16S</strong>SD<br />

+<br />

-<br />

DC IN<br />

DC OUT<br />

RELAY OUT<br />

NC C 1 3 5 7 Vin 21 23 25 27<br />

NC NC 0 2 4 6 C 20 22 24 26 C<br />

(1) NC stands for ”no connect”. Do not use the NC terminals for wire<br />

relaying or branching.<br />

(2) For the connections of the RS-485 communication port (the upper<br />

terminal block), refer to the separate manual “<strong>T1</strong>-<strong>16S</strong> User’s <strong>Manual</strong> -<br />

Communication Function -.<br />

The applicable wire size is 0.3mm 2 (22 AWG) to 1.25mm 2 (16 AWG). The table below<br />

shows the recommended wire size.<br />

Type of signal Recommended wire size<br />

Power 1.25mm 2 (16 AWG)<br />

Grounding 1.25mm 2 (16 AWG)<br />

I/O signals 0.3mm 2 (22 AWG) to 0.75mm 2 (18 AWG)<br />

Basic Hardware and Function 57<br />

<strong>CTi</strong> <strong>Automation</strong> - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net